I/O Allocations In Cqm1 Plcs - Omron C200HW-SRM21-V1 - 08-2007 Operation Manual

Compobus/s system
Hide thumbs Also See for C200HW-SRM21-V1 - 08-2007:
Table of Contents

Advertisement

CQM1-SRM21-V1 Master Unit for CQM1 PLCs
Setting
PLC word
allocation
Pin 1 Pin 2 Pin 3
OFF
OFF
OFF
2 words
(1 IN/1 OUT)
ON
OFF
OFF
4 words
(2 IN/2 OUT)
OFF
ON
OFF
8 words
(4 IN/4 OUT)
ON
ON
OFF
OFF
OFF
ON
2 words
(1 IN/1 OUT)
ON
OFF
ON
4 words
(2 IN/2 OUT)
OFF
ON
ON
8 words
(4 IN/4 OUT)
ON
ON
ON
Note
4-4-3

I/O Allocations in CQM1 PLCs

130
The following table shows all of the possible combinations of DIP switch set-
tings.
Max. number of
I/O points
16 input points,
16 output points
32 input points,
32 output points
64 input points,
64 output points
16 input points,
16 output points
32 input points,
32 output points
64 input points,
64 output points
Note When the CQM1 Master Unit is used in 4-point mode, Slaves with 16 points or
more cannot be used. If Slaves with 16 points or more are used, a data area
overlap error (ERS indicator lit) will occur.
Set the communications mode with DIP switch pin 4 (DR), as shown in the fol-
lowing table.
Pin 4
Communications
mode setting
OFF
High-speed Com-
munications Mode
ON
Long-distance
Communications
Mode
1. Make sure that the communications mode of the Master Unit is the same
as that of all the Slaves. If the CompoBus/S System contains a Slave with
a different communications mode, the COMM indicator on that Slave will
not light, and normal communications with that Slave will not be possible.
Other Slaves will not be adversely affected, and the COMM indicator on the
Master Unit will light normally. For information relating to the states of the
Master Unit indicator, refer to 6-5-1 Indicators .
2. When using a previous Master Unit model (without V1), pin 4 must be set
to OFF. Otherwise, normal communications may not be possible.
3. Pin 4 is factory-set to OFF (High-speed Communications Mode).
4. The settings for the communications distance, baud rate, and communica-
tions cycle time vary according to the setting of pin 4, as shown in the
above table.
In CQM1 PLCs, the Master Unit is treated just like an I/O Unit that has both
inputs and outputs, so the Slave's I/O data is stored in the words allocated to
those inputs and outputs.
Points/n
Usable node
Communications cycle
ode
numbers
number
8 points
IN: 0 and 1
0.5 ms
OUT: 0 and 1
8 points
IN: 0 to 3
0.5 ms
OUT: 0 to 3
8 points
IN: 0 to 7
0.5 ms
OUT: 0 to 7
4 points
IN: 0 to 3
0.5 ms
OUT: 0 to 3
4 points
IN: 0 to 7
0.5 ms
OUT: 0 to 7
4 points
IN: 0 to 15
0.8 ms
OUT: 0 to 15
Communications
Communications
distance
100 m max.
750 kbps
500 m max.
93.75 kbps
Section 4-4
Use of Ana-
time
High-
Long-dis-
speed
tance
Communi-
Communi-
cations
cations
Mode
Mode
4.0 ms
Possible
(Only for
Master Unit
4.0 ms
models with-
V1. Not pos-
4.0 ms
sible for
models with-
out V1.)
4.0 ms
Not possible
4.0 ms
6.0 ms
Communications
baud rate
cycle time
0.5 or 0.8 ms
4.0 or 6.0 ms
log Termi-
nals