Maintenance - Carrier 48NLT Installation, Start-Up And Service Instructions Manual

Table of Contents

Advertisement

to terminals Y and G. These completed circuits through the
thermostat connect contactor coil C (through unit wire Y)
and relay coil IFRl (through unit wire G) across the 24-v
secondary of transformer TRAN.
The normally open contacts of energized contactor C close
and complete the circuit through compressor motor COMP
and condenser fan motor OFM. Both motors start instantly.
The set of normally open contacts of energized relay IFRl
close and complete the circuit through evaporator blower
motor IFM. The blower motor starts instantly.
NOTE: The cooling cycle remains "on" until the room tem¬
perature drops to point that is slightly below the cooling
control setting of the room thermostat. At this point, the
thermostat "breaks" the circuit between thermostat termi¬
nal R to terminals Y and G. These open circuits de¬
energize contactor coil C and relay coil IFRl. The condenser
and compressor motors stop. After a 45-second delay, the
blower motor stops. The unit is in a "standby" condition,
waiting for the next "call for cooling" from the room
thermostat.
Table 10 - Wet Coil Pressure Drop
MODEL
AIRFLOW
(Cfm)
WET COIL PD
(in. wg)
018,024
600
700
800
900
038
.044
.052
062
030
900
1000
1200
.042
.050
.064
036,042
1000
1200
1400
1600
.038
.050
.064
.080
048
1400
1600
1800
050
.060
.072
060
1700
1900
2100
2300
.100
.120
.140
.160
MAINTENANCE
To ensure continuing high performance, and to minimize
the possibility of premature equipment failure, periodic main¬
tenance must be performed on this equipment. This com¬
bination heating/cooling unit should be inspected at least
once each year by a qualified service person. To trouble¬
shoot heating or cooling of units, refer to Tables 11 and 12.
NOTE TO EQ^PMENT OWNER: Consult your local Dealer
about the availability of a maintenance contract.
A
WARNING
The ability to properly perform maintenance on this equip¬
ment requires certain expertise, mechanical skills, tools
and equipment. If you do not possess these, do not at¬
tempt to perform any maintenance on this equipment,
other than those procedures recommended in the Us¬
er's Manual. FAILURE TO HEED THIS WARNING
COULD
RESULT
IN
SERIOUS
PERSONAL
INJURY AND POSSIBLE DAMAGE TO THIS
EQUIPMENT.
_
The minimum maintenance requirements for this equip¬
ment are as follows:
1. Inspect air filter(s) each month. Clean or replace when
necessary.
2. Inspect cooling coil, drain pan and condensate drain each
cooling season for cleanliness. Clean when necessary.
3. Inspect blower motor and wheel for cleanliness and check
lubrication each heating and cooling season. Clean and
lubricate (if required) when necessary.
4. Check electrical connections for tightness and controls
for proper operation each heating and cooling season.
Service when necessary.
5. Check and inspect heating section before each heating
season. Clean and adjust when necessary.
6. Check and clean vent screen if needed.
A
WARNING
Failure to follow these warnings could result in serious
personal injury:
1. Turn off gas supply, then turn off electrical power
to the unit before performing any maintenance or
service on the unit.
2. Use extreme caution when removing panels and parts.
As with any mechanical equipment, personal injury
can result from sharp edges, etc.
3. Never place anything combustible either on, or in
contact with, the unit.
4. Should overheating occur, or the gas supply fail to
shut off, shut off the external main manual gas valve
to the unit, then shut off the electrical supply.
20

Advertisement

Table of Contents
loading

This manual is also suitable for:

48nmt48net48nht48nvt

Table of Contents