Carrier 39T Installation, Start-Up And Service Instructions Manual
Carrier 39T Installation, Start-Up And Service Instructions Manual

Carrier 39T Installation, Start-Up And Service Instructions Manual

Central station air-handling units
Table of Contents

Advertisement

SAFETY CONSIDERATIONS

Air-handling equipment is designed to provide safe and re-
liable service when operated within design specifications. To
avoid injury to personnel and damage to equipment or property
when operating this equipment, use good judgment and follow
safe practices as outlined below.
NEVER enter an enclosed fan cabinet or reach into a unit while
the fan is running.
LOCK OPEN AND TAG the fan motor power disconnect switch
before working on a fan. Take fuses with you and note removal
on tag.
LOCK OPEN AND TAG the electric heat coil power discon-
nect switch before working on or near heaters.
CHECK the assembly and component weights to be sure that
the rigging equipment can handle them safely. Note, also, the
centers of gravity and any specific rigging instructions.
CHECK for adequate ventilation so that fumes will not migrate
through ductwork to occupied spaces when welding or cutting
inside air-handling unit cabinet or plenum.
WHEN STEAM CLEANING COILS be sure that the area is
clear of personnel.
DO NOT remove access panel fasteners until fan is completely
stopped. Pressure developed by a moving fan can cause exces-
sive force against the panel and toward personnel.
DO NOT work on dampers until their operators are
disconnected.
BE SURE that fans are properly grounded before working
on them.
SECURE fan drive sheave with a rope or strap before working
on a fan to ensure that rotor cannot freewheel.
DO NOT restore power to unit until all temporary walkways
inside components have been removed.
NEVER pressurize equipment in excess of specified test
pressures.
PROTECT adjacent flammable material when welding or flame
cutting. Have a fire extinguisher at hand and ready for imme-
diate use.
PREVENT unauthorized entry into the unit; leave safety latches
in place on access doors except during installation or service
procedures. After accessing a section, replace and tighten the
safety latch.
FIELD SUPPLIED MOTORS should be Underwriters' Labo-
ratories (UL) or Canadian Standards Association (CSA)
approved.
FIELD WIRING must comply with National Electrical Code
(NEC) and all local requirements.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 3
PC 201
Catalog No. 533-931
Tab
1b
Central Station Air-Handling Units
Installation, Start-Up and
Service Instructions
Printed in U.S.A.
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . 16-21
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . 22-33
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Rigging And Handling . . . . . . . . . . . . . . . . . . . . . . . 22
Long-Term Storage . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Service Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Drain Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Unit Suspension . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Internal Vibration Isolation . . . . . . . . . . . . . . . . . . . 31
External Vibration Isolation . . . . . . . . . . . . . . . . . . 32
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-72
Connection Flanges . . . . . . . . . . . . . . . . . . . . . . . . . 34
Vertical Draw-Thru Units . . . . . . . . . . . . . . . . . . . . . 35
Field-Assembled Blow-Thru Units . . . . . . . . . . . . 36
Mixing Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Face And Bypass Dampers . . . . . . . . . . . . . . . . . . 37
Fan Motors And Drives . . . . . . . . . . . . . . . . . . . . . . 37
Sheaves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
V-Belts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Inlet Guide Vane Actuators, Forward-Curved
Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Plenum Fan Duct Connections . . . . . . . . . . . . . . . 42
Face And Bypass Damper Linkage . . . . . . . . . . . 44
Mixing Box Damper Actuators . . . . . . . . . . . . . . . 45
Mixing Box/Filter Mixing Box Damper
Linkage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Water and Steam Coil Piping
Recommendations . . . . . . . . . . . . . . . . . . . . . . . . 48
Coil Freeze-Up Protection . . . . . . . . . . . . . . . . . . . 50
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Electric Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72-74
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74-101
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Electric Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Fan Motor Replacement . . . . . . . . . . . . . . . . . . . . . 74
Cleaning Double-Wall Interiors . . . . . . . . . . . . . . . 74
Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Winter Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Coil Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Changing Coil Hand . . . . . . . . . . . . . . . . . . . . . . . . . 79
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Form 39T-3SI
Pg 1
39T
Page
3-99
Replaces: 39T-2SI

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 39T

  • Page 1 (NEC) and all local requirements. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 3 PC 201 Catalog No. 533-931 Printed in U.S.A. Form 39T-3SI Pg 1 3-99 Replaces: 39T-2SI...
  • Page 2 Forward-Curved Fans ..... 91 for all 39T units. Each unit’s model number is listed on a Lubrication ....... . . 97 label affixed to the fan section.
  • Page 3 Table 1 — Component Description 39T (Horizontal) and (Vertical) 39T Return Fan Components Unit Components UNIT SIZE COMPONENT DESCRIPTION AVAILABILITY UNIT SIZE COMPONENT DESCRIPTION AVAILABILITY Exhaust Box (standard EXB1 07-92 dampers) ACC1 Access (upstream location) 07-92 Exhaust Box (premium Airfoil Fan, Horizontal...
  • Page 4 SEP SHIP — Separate Shipped VERT — Vertical NOTES: 1. Contact your Carrier sales representative for the AHU Builder™ program. 2. See Table 1 on page 3 for component descriptions and recommended section sequences. 3. All components have individual base rails.
  • Page 5 Face and bypass dampers configured with adjacent coil and ac- cess (external only). *Contact your Carrier sales representative for factory-installed op- BCF1/BCF3 accepts bag filters up to 12-in. long. To use longer tion (FIOP) and/or coil component sequences available from the factory using the AHU Builder™...
  • Page 6 39T FIOPS* 39T COILS* ANG1 FCS3 ACC1 39T FANS MBX1,5,6,7 BCF1 ACC1 MCS1 AFS3 MHS1 ACC1 AMX1 FLT1 EHS1 FMB1,2,3,4 LCS1 39TU FAN PAF3 MHS1 SIZES 07-26 Fig. 2 — Recommended Section Sequences, Horizontal Draw-Thru (Without Face and Bypass Section)
  • Page 7 39T FIOPS* COILS* ANG1 FCS3 BCF1 ACC1 ACC1 MCS1 FANS MXB1,5,6,7 AFS3 MHS1 FLT1 EHS1 LCS1 ACC1 AMX1 FB1,2,3,4 39TU PAF3 MHS1 SIZES 32-92 Fig. 2 — Recommended Section Sequences, Horizontal Draw-Thru (Without Face and Bypass Section) (cont)
  • Page 8 39T---A THROUGH 39T FIOPS* COILS* 39T---E MCS1 BPH1 BCC2 ANG1 FCS3 FBH1 MXB1,5,6,7 FANS LCS1 MHS1 BCF1 FBC1 AFS3 ACC1 ACC1 AMX1 FMB1,2,3,4 FLT1 EHS1 BCC2 BPH1 39TU FBH2 PAF3 ACC1 MHS1 SIZES 07-26 Fig. 3 — Recommended Section Sequences, Horizontal Draw-Thru...
  • Page 9 39T---A THROUGH 39T FIOPS* 39T---E COILS* BPH1 BCC2 39TU FBH1 LCS1 PAF3 MXB1,5,6,7 ANG1 MHS1 FBC1 ACC1 BCF1 11 11 ACC1 FCS3 AMX1 EHS1 FMB1,2,3,4 FANS FLT1 FBH2 MCS1 AFS3 BPH1 BCC2 2 MHS1 SIZES 32-92 Fig. 3 — Recommended Section Sequences, Horizontal Draw-Thru...
  • Page 10 DOWNSTREAM COMPONENTS 39T FIOPS* NOT AVAILABLE FANS AFS4, FCS4 MHS1 BCF1 MXB1,5,6,7 FLT1 EHS1 LCS1 AMX1 VCS1 FMB1,2,3,4 ACC1 ACC1 COILS* ANG1 ACC1 VCS2,3 MCS1 SIZES 07-26 Fig. 4 — Recommended Section Sequences, Vertical Draw-Thru (Without Face and Bypass Section)
  • Page 11 DOWNSTREAM COMPONENTS NOT AVAILABLE 39T FIOPS* FANS AFS4, FCS4 BCF1 MHS1 MXB1,5,6,7 MCS1 9 EHS1 FLT1 15 ACC1 AMX1 COILS* FMB1,2,3,4 VCS1 ACC1 LCS1 ANG1 ACC1 VCS2,3 SIZES 32-61 Fig. 4 — Recommended Section Sequences, Vertical Draw-Thru (Without Face and Bypass Section) (cont)
  • Page 12 DOWNSTREAM COMPONENTS 39T---A AND NOT AVAILABLE 39T FIOPS* 39T---E FANS BCF1 AFS4, FCS4 FBH1 MHS1 MXB1,5,6,7 BPH1 EHS1 MCS1 FBC1 11 11 15 ACC1 FLT1 ACC1 AMX1 FMB1,2,3,4 VCS1 COILS* ACC1 LCS1 FBH2 ANG1 VCS2,3 SIZES 07-26 Fig. 5 — Recommended Section Sequences, Vertical Draw-Thru...
  • Page 13 39T---A AND 39T FIOPS* 39T---E DOWNSTREAM CONPONENTS NOT AVAILABLE FANS BCF1 AFS4, FCS4 FBH1 MXB1,5,6,7 BPH1 MCS1 MHS1 9 EHS1 COILS* ACC1 VCS1 FBC1 AMX1 FMB1,2,3,4 15 ACC1 LCS1 ACC1 FLT1 VCS2,3 FBH2 ANG1 SIZES 32-61 Fig. 5 — Recommended Section Sequences, Vertical Draw-Thru...
  • Page 14 39T FIOPS* 39T9 ACC2 39T FANS (AFS AND FCS) ZDS1 ANG1 BCS1 ZDS2 FCS5 EHS1 MXB1,5,6,7 BCF1 AFS5 BCS2 ACC1 AMX1 FMB1,2,3,4 FLT1 MHS1 BCS3 PAF5 ACC1 BCS4 39TU BCF3 ACC2 BCS7 BCF3 Fig. 6 — Recommended Section Sequences, Blow-Thru — Sizes 07-92...
  • Page 15 39TU PAF5 EXHAUST AIR TO OTHER RAF2 ARRANGEMENTS RFC2 EXB1,2 39T UNIT Fig. 7 — Recommended Section Sequences, Return-Air and Exhaust — Sizes 07-92...
  • Page 16 PHYSICAL DATA Data describing the physical properties of 39T coils and fans is provided in Tables 2-12. Table 2 — Coil Capacity and Size 39T UNIT SIZE CHILLED WATER/ DIRECT EXPANSION Large Face Area Nominal Capacity (cfm) 3688 4921 5748...
  • Page 17 Table 2 — Coil Capacity and Size (cont) 39T UNIT SIZE CHILLED WATER/ DIRECT EXPANSION Large Face Area Nominal Capacity (cfm) 17,898 21,334 27,052 33,446 40,567 50,401 at 550 fpm ⁄ x 27 ⁄ ⁄ x 30 ⁄ x 35 (U) 113 x 37 ⁄...
  • Page 18 Small Face Area 1-Row 2-Row Bypass Face Area 1-Row 2-Row 11.5 NOTE: One gallon of water weighs 8.33 lbs. Table 4 — Chilled Water Coil Connection Sizes 39T UNIT SIZE CIRCUIT FACE TYPE AREA Nozzle Size (in. MPT) LARGE, HALF ⁄...
  • Page 19 Table 6 — Steam Coil Connection Sizes 39T UNIT SIZE FACE CONNECTION AREA Nozzle Size (in. MPT) Inlet — — — — — — LARGE Outlet — — — — — — Inlet — — — — — — —...
  • Page 20 Table 9 — Airfoil Fan Physical Data 39T UNIT SIZE WHEEL DIAMETER (in.) ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ MAX SPEED (rpm) 4300 4000 3700 3200 2700 2700 2400 2100 1925 1500 1350 1200 1200 FAN SHEAVE BORE (in.)
  • Page 21 Table 11 — Plenum Fan Physical Data, Standard Wheel 39T UNIT SIZE WHEEL DIAMETER (in.) ⁄ ⁄ ⁄ ⁄ ⁄ MAX SPEED (rpm) 3122 2848 2560 2020 1818 1818 1473 1335 1208 1097 FAN SHEAVE BORE (in.) ⁄ ⁄ ⁄...
  • Page 22 Do not remove the cover or coil 108 inches. All 39T units can be rigged using the lifting brack- connection caps until you install the unit.
  • Page 23 07-26 SIZE UNITS 32-92 SIZE UNITS NOTES: LIFTING SLOT [60] SIZE 07-61 [38] x [51] LG = Isolator Locations. [27] SIZE 74, 92 2. (_ _ _ _) mm ÷ 25.4 = (_ _ _ _) in. [46] SIZE 07-61 3.
  • Page 24 Table 13 — Motor Weights (Lb) 230/460-3-60 200/400-3-50* 575-3-60 TEFC TEFC TEFC E+/E+3 † † † † 0.75 † † † † 60/ 68 60/ 66 65/ 66 89/ 99 142/158 154/200 250/259 287/290 394/368 436/436 416† 470† 661/661 403† 527†...
  • Page 25 Table 14 — Component Weights (Lb) (Single-Wall Casing)* 39T UNIT SIZE SECTION COMPONENT† TYPE AFS3 1050 1300 AFS4 1050 1300 AFS5 1050 1300 FCS3 1000 1350 FCS4 1000 1350 FCS5 1000 1350 PAF3 — — 1025 1160 1415 PAF5 —...
  • Page 26 Table 14 — Component Weights (Lb) (Single-Wall Casing)* (cont) 39T UNIT SIZE SECTION COMPONENT† TYPE AFS3 1776 1957 2415 2840 3304 3880 AFS4 1776 1957 2415 2840 3304 3880 AFS5 1776 1957 2415 2840 3304 3880 FCS3 1654 1825 2180 2479 —...
  • Page 27 Table 15 — Dry Coil Weights (Lb) 39T UNIT SIZE COIL FACE FINS ROWS TYPE AREA PER IN. 1183 1001 1225 1035 1266 1062 1308 1385 1696 1100 1356 1436 1759 1139 1405 1487 1821 LARGE 1007 1372 1695 1795...
  • Page 28 Service Clearance — Drain Positioning — When planning the placement To prevent build-up of conden- of the unit, ensure adequate space for service access. Typical sate in the drain pan and ensure proper operation of the drain service operations can require removing the coils and filters system, position the unit so that condensate is properly trapped.
  • Page 29 Service Area Dimensions (ft-in.) UNIT SIZE VCS1 BPH1, MHS1 ⁄ 5- 6 ⁄ ⁄ ⁄ ⁄ 5-10 ⁄ ⁄ ⁄ ⁄ ⁄ 6- 6 ⁄ ⁄ ⁄ ⁄ 7- 2 ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ 7- 6 ⁄ ⁄ ⁄...
  • Page 30 Service Area Dimensions (ft-in.) 39T UNIT SIZE BCS1, 2, 3, 4, 7 ⁄ 5- 6 ⁄ ⁄ ⁄ ⁄ 5-10 ⁄ ⁄ ⁄ ⁄ 6- 6 ⁄ ⁄ ⁄ ⁄ 7- 2 ⁄ ⁄ ⁄ ⁄ 7- 6 ⁄ ⁄...
  • Page 31 SERVICE AREA DIMENSIONS (ft-in.) 39T UNIT 39T UNIT SIZE SIZE ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ 10-4 ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ 11-8 ⁄ ⁄ ⁄ ⁄ 2-11 ⁄...
  • Page 32 ADJUSTING ISOLATOR SPRINGS, AIRFOIL AND 3. Tighten the locknut. FORWARD-CURVED FANS — Units with factory-supplied 4. Repeat for each of the isolator springs and ensure that the motors and drives are preset to ⁄ ± ⁄ -in. clearance be- fan sled is floating on the springs. tween the base frame assembly and the bottom panels;...
  • Page 33 PLAN VIEW HOLDDOWN BRACKET SCREW LOCATIONS Fig. 15 — Removing Holddown Bracket and Adjustment of Isolator Spring, Airfoil and Forward-Curved Fans ADJUSTABLE STEM LOCKNUT DOOR FRAME AND SIDE PANEL(S) MOTOR BASE ISOLATOR SPRING, REF J-BOLT (REMOVE COMPLETELY) SHEET METAL SCREWS BOTTOM PANEL OR DOUBLE WALL SHEET METAL SCREWS Fig.
  • Page 34 Connection flanges provide a means of separating unit sections. The first and last com- This section describes how to install 39T units, compo- ponents in an assembly also have connection flanges if they nents, and component parts. Units specified on a single or- can be connected to other components.
  • Page 35 DIMENSIONS (ft-in.) UNIT BCS1 BCS2 BCS1 BCS2 BCS1 BCS2 BCS3 BCS4 SIZE (Opening) Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical Discharge Discharge Discharge Discharge Discharge Discharge discharge Discahrge 4- 0 ⁄ 0-10 ⁄ ⁄ 0- 7 ⁄ ⁄ ⁄ ⁄...
  • Page 36 3. An attachment angle is located on the upstream side of Field Assembled Blow-Thru Units — Both single- the cooling section. Keep the angle in place; it aligns the and multi-zone units are built for horizontal intake and dis- heating section with the cooling section. charge.
  • Page 37 Fig. 22 — Zone Damper Assembly Details (Horizontal Discharge Shown) Mixing Box — Fan Motors and Drives — Attach the ductwork to the mixing box When installing motors in panels with sheet metal screws as shown in Fig. 23. Duct- the field, locate the electrical junction box toward the center work should be flanged out as close to the damper frame as of the unit.
  • Page 38 Sheaves — Factory-supplied drives are prealigned and tensioned, however, Carrier recommends that you check the belt tension and alignment before starting the unit. Always check the drive alignment after adjusting belt tension.
  • Page 39 6. On current production, the correct tension information is listed on the fan drive label (see Fig. 27). For older equip- ment or for units with field-modified drives, use the de- flection formula given in the example below and the ten- sion data from Fig.
  • Page 40 DIRECT-COUPLED ACTUATOR INSTALLATION Inlet Guide Vane Actuators, Forward-Curved Fans — Inlet guide vanes (IGVs) are available as options 1. Disconnect power to the fan motor prior to performing on forward-curved fans. They must be adjusted in the field the installation. as follows.
  • Page 41 CONNECTING ACTUATOR JACKSHAFT INLET GUIDE ANTI-ROTATION VANES (IGV) NOTE: When the unit is not operating, vanes may not fully close. This STRAP condition is normal. During unit operation, airflow and pressure differential help to control and close the vanes. Fig. 31 — IGV Actuator Mounting Fig.
  • Page 42 Total Torque Required (in.-lb) = A ( + B x ESP + C, per the explanation in the 39T Product Data manual. 1000 • Locate discharge openings on the side or top panels be- where cfm is the design airflow and ESP is the external static pres-...
  • Page 43 Fig. 34 — Discharge Fabrication, Draw-Thru Plenum Fans...
  • Page 44 Sizes 74 and 92 have 3 damper assemblies linked by direct connected. For direct conection actuators remove factory- two jackshafts. installed crankcarm. See Table 18 for operating torque requirements. Table 18 — Damper Operating Torque (lb-in.) 39T UNIT SIZE DAMPER SECTION MXB* BOTH DAMPERS INTERCONNECTED...
  • Page 45 Mixing Box Damper Actuators — The 39T mixing reinstalled on the rear damper. The linkages must also be boxes are supplied with low-leak dampers and blade and edge readjusted for proper operation. Refer to the Field Supplied seals.
  • Page 46 OUTDOOR AIR DAMPER MIXING BOX (CW OPENING) PARALLEL AXIS ACTUATOR BETWEEN DAMPERS 30 DEGREES CCW FROM PERPENDICULAR AXIS RETURN AIR DAMPER (CW OPENING) CONNECTING ROD 30 DEGREES CW TYPICAL DAMPER FROM PARALLEL SECONDARY LINKAGE AXIS TYPICAL DAMPER SECONDARY LINKAGE LEGEND CCW —...
  • Page 47 Fig. 38 — Mixing Box/Filter Mixing Box, Sizes 26-92 — Typical Damper Arrangement (Top and Rear) Fig. 39 — Mixing Box/Filter Mixing Box, Sizes 26-92 — Typical Damper Arrangement (Bottom and Rear)
  • Page 48 Piping practices are outlined in the Carrier System De- • To lift condensate above the coil return line into overhead sign Manual, Part 3, Piping Design.
  • Page 49 Fig. 41 — Coil Connections and Lifting Points Fig. 42 — Steam Coil PIping...
  • Page 50 For best up. Install a coil freeze-up thermostat to shut down the sys- performance, use Carrier’s AHU Builder™ program to se- tem if any air temperature below 36 F is encountered enter- lect nozzle sizes for each unit and replace the factory- ing the water coil.
  • Page 51 Table 20 — Direct Expansion Coil Circuiting Data LARGE FACE AREA COILS 39T UNIT SIZE CIRCUITING TYPE Quarter Half Full Half Full Half Full Double Half Full Double Airflow (cfm) at 550 fpm 3688 4921 5748 7173 Total Face Area (sq ft) 10.5...
  • Page 52 Table 20 — Direct Expansion Coil Circuiting Data (cont) LARGE FACE AREA COILS (cont) 39T UNIT SIZE CIRCUITING TYPE Half Full Double Half Full Double Half Full Double Airflow (cfm) at 550 fpm 8895 11,439 14,215 Total Face Area (sq ft) 16.2...
  • Page 53 Table 20 — Direct Expansion Coil Circuiting Data (cont) LARGE FACE AREA COILS (cont) 39T UNIT SIZE CIRCUITING TYPE Half Full Double Half Full Double Half Full Double Airflow (cfm) at 550 fpm 17,898 21,334 27,052 Total Face Area (sq ft) 32.5...
  • Page 54 Table 20 — Direct Expansion Coil Circuiting Data (cont) LARGE FACE AREA COILS (cont) 39T UNIT SIZE CIRCUITING TYPE Half Full Double Half Full Double Half Full Double Airflow (cfm) at 550 fpm 33,446 40,567 50,401 Total Face Area (sq ft) 60.8...
  • Page 55 Table 20 — Direct Expansion Coil Circuiting Data (cont) MEDIUM FACE AREA COILS 39T UNIT SIZE CIRCUITING TYPE Quarter Half Full Half Full Half Full Double Half Full Double Airflow (cfm) at 550 fpm 2868 4026 4703 5977 Total Face Area (sq ft) 10.9...
  • Page 56 Table 20 — Direct Expansion Coil Circuiting Data (cont) MEDIUM FACE AREA COILS (cont) 39T UNIT SIZE CIRCUITING TYPE Half Full Double Half Full Double Half Full Double Airlfow (cfm) at 550 fpm 6989 9420 11,970 Total Face Area (sq ft) 12.7...
  • Page 57 Table 20 — Direct Expansion Coil Circuiting Data (cont) MEDIUM FACE AREA COILS (cont) 39T UNIT SIZE CIRCUITING TYPE Half Full Double Half Full Double Half Full Double Airflow (cfm) at 550 fpm 14,785 17,067 21,255 Total Face Area (sq ft) 26.9...
  • Page 58 Table 20 — Direct Expansion Coil Data (cont) MEDIUM FACE AREA COILS (cont) 39T UNIT SIZE CIRCUITING TYPE Half Full Double Half Full Double Half Full Double Airflow (cfm) at 550 fpm 26,973 33,191 40,567 Total Face Area (sq ft) 49.0...
  • Page 59 On face split coils with unequal size condensing units, the largest condensing unit should be connected to the largest LEGEND coil (always the bottom coil on 39T units). This line is nor- mally the first-on, last-off circuit. TXV — Thermostatic Expansion Valve Fig.
  • Page 60 1300 to 1500 F. Extension nipple should be as short as possible. Fig. 48 — Nozzle Change-Out Table 21 — Auxiliary Side Connector (Hot Gas Bypass) Data CONNECTION SIZES (in.) SPORLAN CARRIER USED WITH SPORLAN NOZZLE TYPE PART NO. DISTRIBUTOR TYPE SIZE Inlet —...
  • Page 61 SPECIAL PIPING WITH 4 SPLITS PER COIL Manifolding for 2-Face Splits— Refer to Fig. 50 and exter- nally manifold as follows: 1. Connect the 4 expansion valves to the 4 distributors on each coil and connect the 4 suction lines to the 15-diameter-long risers as outlined in previous piping instructions.
  • Page 62 LEGEND TXV — Thermostatic Expansion Valve Fig. 51 — Row-Split Coil Manifolding (Typical) SPECIAL PIPING FOR DOUBLE-CIRCUIT COILS — All 3. Repeat Step 2 for lower face split using third and fourth 8-row coils that are double circuited require special piping distributor and suction connections.
  • Page 63 LEGEND TXV — Thermostatic Expansion Valve Fig. 52 — Double-Circuited Face Split Coil Manifolding — Coils with Less Than 34 Tubes in Face (Typical) LEGEND TXV — Thermostatic Expansion Valve Fig. 53 — Double-Circuited Face Split Coil Manifolding — Coils with More Than 34 Tubes in Face (Typical)
  • Page 64 LEGEND TXV — Thermostatic Expansion Valve Fig. 54 — Double-Circuited Row Split Coil Manifolding — Coils with Less Than 34 Tubes in Face (Typical) LEGEND TXV — Thermostatic Expansion Valve Fig. 55 — Double-Circuited Row Split Coil Manifolding — Coils with More Than 34 Tubes in Face (Typical)
  • Page 65 To determine the trap dimensions for blow-thru units, find Condensate Drain — Install a condensate-trapping drain the coil’s maximum positive pressure (P in Fig. 57). This line at the unit’s drain connection; use 1 ⁄ -in. standard pipe. figure is normally the fan total static pressure (P = fan total See Fig.
  • Page 66 CONNECT POWER AND CONTROL WIRES — Heater Electric Heaters — Electric heaters are factory in- wiring schematic is located on control box panel. (Figure 59 stalled. If special circumstances require field installation of shows typical wiring details.) Electrical data for each heaters, follow the instructions given below.
  • Page 67 Each heater has 2 different types of factory-installed ther- thermal cutout is load carrying and is installed in each heater mal cutouts for overtemperature protection; an automatic subcircuit. The primary and secondary overtemperature pro- reset thermal cutout for primary protection and a manual tection systems are independent of each other.
  • Page 68 Table 22 — Electric Heater Data, Horizontal Heaters Used in EHS1 POWER SUPPLY, 3-PHASE CIRCUITS HEATER NO. OF HEATER TEMP MIN COIL AREA CONTROL COIL RISE FACE VEL 208 Volts 240 Volts UNIT SIZE (Sq Ft) STEPS (°F) (Fpm) Total FLA No.
  • Page 69 Table 22 — Electric Heater Data, Horizontal Heaters Used in EHS1 (cont) POWER SUPPLY, 3-PHASE CIRCUITS HEATER NO. OF HEATER TEMP MIN COIL AREA CONTROL COIL RISE FACE VEL 208 Volts 240 Volts UNIT SIZE (Sq Ft) STEPS (°F) (Fpm) Total FLA No.
  • Page 70 Table 22 — Electric Heater Data, Horizontal Heaters Used in EHS1 (cont) POWER SUPPLY, 3-PHASE CIRCUITS HEATER NO. OF HEATER TEMP MIN COIL AREA CONTROL COIL RISE FACE VEL 480 Volts 600 Volts UNIT SIZE (Sq Ft) STEPS (°F) (Fpm) Total FLA No.
  • Page 71 Table 22 — Electric Heater Data, Horizontal Heaters Used in EHS1 (cont) POWER SUPPLY, 3-PHASE CIRCUITS HEATER NO. OF HEATER TEMP MIN COIL AREA CONTROL COIL RISE FACE VEL 480 Volts 600 Volts UNIT SIZE (Sq Ft) STEPS (°F) (Fpm) Total FLA No.
  • Page 72 Table 23 — Field Wiring for Incoming Conductors 7. Check fan speed with a strobe-type tachometer or use the Sized for 125% of Heater Load following formula: Obtain the motor rpm from the fan motor nameplate and LOAD AMPS* LOAD AMPS* WIRE SIZE WIRE SIZE read sheave pitch diameters marked on the fan and motor...
  • Page 73 ROLLER — EXTENDED RACE, ONE OR BOTH SIDES SQUEEZE-TYPE LOCKING COLLAR DRIVE PULLEY TORQUE TABLE NOMINAL TORQUE CAPSCREW AND HEX HEAD SQUARE HD SCREW SIZE (in.-lb) SETSCREW ACROSS ACROSS TORQUE SIZE (no/in.) FLATS (in.) FLATS (in.) No. 6 No. 8 ⁄...
  • Page 74 COILS Electric Heaters — At least once a year at start of op- erating season or whenever unit is serviced, check field and Chilled Water Coil — Typical coil vents, drains, and lifting factory-made electrical connections for tightness. Also pe- points are shown in Fig.
  • Page 75 6. If solution is too weak, add more antifreeze until desired Winter Shutdown — It is recommended that auxiliary strength is reached, then circulate solution through coil drain piping be added to coil piping if yearly winterizing of for 15 minutes or until concentration is satisfactory. coils is anticipated.
  • Page 76 3. Slide the coil cover panel off the coil nozzles. Coil Removal 4. Remove coil panels, as required, on both sides. COOLING AND HEATING COILS — See Fig. 62 for unit 5. Remove header and return baffle screws, leaving baffle with single coil or Fig.
  • Page 77 LEGEND 1 — Accessory Side Panel 6 — Right Side Panels 2 — Left Side Panels 7 — Inside Baffle 3 — Top Panels 8 — Horizontal Baffle 4 — Baffle Angle Screw 9 — Upper Condensate Pan 5 — Piping 10 —...
  • Page 78 Fig. 64 — Blow-Thru Unit — Coil Removal Fig. 65 — Plan View — Typical Coil...
  • Page 79 See Fig. 67 for typical track for bag-cartridge filter sec- Changing Coil Hand tion used on draw-thru unit (BCF1). NOTE: Electric heat, chilled water, and hot water coil hand FLAT FILTERS — Flat filter section accommodates 2-in. or cannot be changed. 4-in.
  • Page 80 Table 25 — Filter Data 39T UNIT SIZE FLAT FILTER (FLT1) Cell Size (in.) 20x20x2 or 20x20x4 Quantity — — — — — — Cell Size (in.) 16x25x2 or 16x25x4 Quantity — — — — Cell Size (in.) 20x25x2 or 20x25x4 Quantity —...
  • Page 81 Fig. 68 — Filter Arrangement — 2-in. and 4-in. Flat...
  • Page 82 Fig. 68 — Filter Arrangement — 2-in. and 4-in. Flat (cont)
  • Page 83 Fig. 69 — Filter Arrangement — Angle Filters (2-in. Only)
  • Page 84 Fig. 69 — Filter Arrangement — Angle Filters (2-in. Only) (cont)
  • Page 85 Fig. 70 — Filter Arrangement — BCF1 Bag or Cartridge (Draw-Thru)
  • Page 86 Fig. 70 — Filter Arrangement — BCF1 Bag or Cartridge (Draw-Thru) (cont)
  • Page 87 Fig. 71 — Filter Arrangement — BCF3 Bag or Cartridge (Blow-Thru)
  • Page 88 Fig. 71 — Filter Arrangement — BCF3 Bag or Cartridge (Blow-Thru) (cont)
  • Page 89 -.001 It should not be necessary to drive a new bearing nominal. Carrier specified parts are recommended. onto shaft. If light tapping is needed, do not tap against outer race. 9. Check fan shaft diameter at bearing mount. If worn by more than 0.001 in.
  • Page 90 AIRFOIL FANS FORWARD-CURVED FANS Cutoff Cutoff UNIT Wheel Size Cutoff Wheel Size Cutoff Clearance Clearance SIZE (Diam) (Diam) ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄...
  • Page 91 UBF: Curved Fans — If field modification of discharge po- sition is required, 39T airfoil and forward-curved fans may 1. Remove the screws holding the long and short bearing- be converted to any standard discharge and hand without any support channels and fan housing to the base member.
  • Page 92 NOTE: ‘‘A’’ frame shown shaded. Fig. 74 — Fan Discharge Positions...
  • Page 93 TOP HORIZONTAL FRONT ARRANGEMENT SHOWN (ASSEMBLED RIGHT HAND) SIZES 07-26 TOP HORIZONTAL FRONT ARRANGEMENT SHOWN (ASSEMBLED RIGHT HAND) SIZES 32-92 Fig. 75 — Scroll Assembly — Airfoil Fan Without IGV...
  • Page 94 TOP HORIZONTAL FRONT/REAR ARRANGEMENT SHOWN (ASSEMBLED RIGHT HAND) SIZES 07-26 TOP HORIZONTAL FRONT/REAR ARRANGEMENT SHOWN (ASSEMBLED RIGHT HAND) SIZES 32-61 Fig. 76 — Scroll Assembly — Forward-Curved Fan Without IGV...
  • Page 95 NOTE: Inlet guide vanes are attached to the fan housing so that the ball joint in view ‘U’ is in the 12 o’clock position with the vanes at 45 degrees. (For upblast discharge units, the ball joint is at the 9 o’clock position.) TOP HORIZONTAL FRONT/REAR ARRANGEMENT SHOWN...
  • Page 96 NOTE: For any discharge position, install vane assembly to provide control arm movement from closed to open in same direction as wheel rotation. Locate IGVs in fan housing so that control arm is vertical when pulled back toward jackshaft as far as control arm will travel. TOP HORIZONTAL FRONT ARRANGEMENT SHOWN (ASSEMBLED RIGHT HAND)
  • Page 97 Lubrication MOTORS — Lubricate in accordance with nameplate at- tached to motor or with manufacturer’s recommendations in- cluded with motor. BEARINGS Fan Bearings — Lubricate fan bearings every 3 months with suitable bearing grease. Typical lubricants are given in Table 26. Porous Bronze Bearings —...
  • Page 98 NOTE: Assembly shown for Top Horizontal Front, Top Horizontal Rear, Upblast Front, and Upblast Rear. SIZES 07-26 NOTE: Assembly shown for Top Horizontal Front, Upblast Front, and Downblast Rear. SIZES 32-92 Fig. 80 — Motor Bases...
  • Page 99 Table 27 — Motor and Drive Package Data, Forward-Curved Fans FAN DISCHARGE FAN DISCHARGE THF/THR UBF/UBR THF/THR UBF/UBR UNIT MOTOR UNIT MOTOR SIZE FRAME SIZE FRAME Centerline Distance (in.) Centerline Distance (in.) 143T 11.1 184T 14.4 17.2 19.3 21.3 145T 11.1 213T 14.0...
  • Page 100 Table 28 — Motor and Drive Package Data, Airfoil Fan FAN DISCHARGE FAN DISCHARGE THF/THR UBF/UBR THF/THR UBF/UBR UNIT MOTOR UNIT MOTOR SIZE FRAME SIZE FRAME Centerline Distance (in.) Centerline Distance (in.) 143T 11.1 213T 16.2 18.9 21.0 23.0 145T 11.1 215T 16.2...
  • Page 101 Table 29 — Motor and Drive Package Data, Plenum Fan FAN WHEEL FAN WHEEL Small Standard Small Standard UNIT MOTOR UNIT MOTOR SIZE FRAME SIZE FRAME Centerline Distance (in.) Centerline Distance (in.) 143T — — 20.6 23.6 145T 37.6 40.4 42.1 44.9 145T...
  • Page 104 METRIC CONVERSION CHART Copyright 1999 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 3 PC 201 Catalog No. 533-931 Printed in U.S.A. Form 39T-3SI Pg 104...

Table of Contents