Polypropelene Vent System Installation - Patterson-Kelley P-K STORM ST-8000 Installation And Owner's Manual

Table of Contents

Advertisement

Operating Parameters:
Maximum Water Temperature Set Point 180°F
Flue Gas Limit 194°F
Installation Parameters:
Cement and primer must conform to ASTM F493
Three feet of venting closest to the boiler must not be enclosed
The vent shall not be insulated

PolyPropelene Vent System Installation

Install PolyPropelene vent systems in accordance with this manual. Install manufactured vent systems
in accordance with the manufacturer's listing and instructions. A customer supplied adapter is required
to be installed between the boiler and the PolyPropelene venting.
Model
ST2500-ST3000
ST3500-ST4000
ST5000-ST8000
*Requires 14" to 12" reducer 2691000373
Revised: February 2, 2024
Released: February 2, 2024
CPVC Support Spacing (Feet)
Vent Size
Sch. 80
4
4-1/2
6
5
8
5-1/2
10
6
12
6-1/2
Centrotherm
Innoflue
Adapter
Size
Model
10"
ISSA1010
12"
ISSA1212
14"
ISSA1212*
 Patterson-Kelley 2024
All Rights Reserved.
®
P-K Storm
Gas Fired Boiler
Technical Service 1.877.728.5351
2691000403 P-K Storm ST2500-ST8000
Installation and Owners Manual Rev G.docx
Page 43