Category II or IV Venting Installation

P-K STORM
®
boilers are dual certified as Category II or IV appliances, as defined in ANSI Z21.13/CSA
4.9, latest edition and are not suitable for use with Type "B" Vents.
and Canada is listed in the Table of Acceptable Materials for Venting Systems located in 2.5.4.
Vent installations shall be in accordance with NFPA 54/ANSI Z223.1, the National Fuel Gas Code, or
CAN/ CSA-B149.1, the Natural Gas and Propane Installation Code, or applicable provisions of the local
building codes.
The combustion air flow rate requirements per boiler model are summarized in 3.4.3. When sizing the
combustion air intake ductwork, the pressure drop through this ductwork MUST NOT exceed 0.22"
W.C. for the 2500-4000 and MUST NOT exceed 0.5" W.C. for the 5000-8000 as described in the table
below:
®
P-K STORM
Boiler Model
ST-2500, ST-3000, ST-3500,
ST-4000
ST-5000, ST-6000, ST-8000
ST-2500, ST-3000, ST-3500,
ST-4000
ST-5000, ST-6000, ST-8000
If the combustion air intake ductwork and the exhaust vent terminate on the same wall of
NOTE:
the building, they must utilize the same type of termination fitting.
Patterson-Kelley recommends including a motorized combustion air damper in each
NOTE:
appliance's air intake ductwork. Refer to
NOTE: ST-2500-ST-4000: Total combined vent pressure not to exceed 0.44" W.C.
ST-5000-ST-8000: Total combined vent pressure not to exceed 1.0" W.C.
Revised: February 2, 2024
Released: February 2, 2024
Maximum Allowable
Flue Vent Category
through Combustion
II
II
IV
IV
3.4.3
below for
 Patterson-Kelley 2024
All Rights Reserved.
P-K Storm
Technical Service 1.877.728.5351
The vent material to be used for US
Pressure Drop
Allowable Vent Pressure
Air Ductwork
0.22" W.C.
0.5" W.C.
+0.01" W.C to +0.44"
0.22" W.C.
0.5" W.C.
+0.01" W.C to +1.0" W.C.
more information.
2691000403 P-K Storm ST2500-ST8000
Installation and Owners Manual Rev G.docx
®
Gas Fired Boiler
-0.01" W.C. to
-0.05" W.C.
-0.01" W.C. to
-0.05" W.C.
W.C.