Daikin Perfera ARXM25A Service Manual page 55

Table of Contents

Advertisement

To check if the refrigerant circuit is correctly charged
RXM20~50A + ARXM25~50A + FTXM20~50A + ATXM20~50A + CTXM15A
Split Perfera ZETA R32
ESIE23-06 – 2023.12
Temperature drop found?
No
Due to the relationship to pressure control and electronic expansion valve control,
the amount of refrigerant needs to be examined according to operating conditions.
Refer to the procedures shown below for correct examination.
Refrigerant overcharge diagnosis
1 High pressure rises. Consequently, overload control is conducted to cause
insufficient cooling capacity.
2 The superheated degree of suction gas lowers (or the wet operation is
performed). Consequently, the compressor consumes more power and is
noisy (before over‑current relay trips).
3 The subcooling degree of refrigerant in liquid form rises (values >4~5K are
NOT normal).
Cooling
High pressure drooping control
High pressure gradually rises with
increasing operating frequency.
High
pressure
(Low pressure is maintained
Low
at a certain level.)
pressure
Operating
frequency
To maintain low pressure, operating
frequency increases on the capacity control.
(Degree of overcharge)
Proper amount
4
|
Third party components
Action
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Operating frequency comes to
the lowest level.
Subcooling degree becomes
higher. (The temperature of
liquid connection piping
becomes lower.)
Low pressure rises with lowering
compressor output.
Further overcharge
draft – 21/12/2023 13:09
Service manual
55