Check
Check the defrost operation ferquency in
Heat mode

3.6.4 Operating noise and vibrations

Check
Check the installation conditions (specified
in the installation manual).
RXM20~50A + ARXM25~50A + FTXM20~50A + ATXM20~50A + CTXM15A
Split Perfera ZETA R32
ESIE23-06 – 2023.12
Detail
Check if the defrost operation frequency is
normal according to the outdoor ambient
temperature and outdoor heat exchanger
temperature (Values depend on the
models).
If the product goes to defrost frequently:
-
Possible problem: Low amount of
refrigerant.
-
Check refrigerant amount and add
more if necessary.
If the product does NOT go to defrost
frequently:
-
Possible problem: Sensor broken.
-
Check thermistors.
Detail
Use general vibration prevention where
needed.
If the mounting wall is too thin, you must
use cushion material or rubber, or change
the installation place.
Refrigerant piping is too short; is the
length within specified range?
Due to bad installation or general
conditions there may be deformation of
the unit.
Are all the screws installed and tightened
properly?
Is all piping secured, fixed and supported
by inserting a cushion material where
needed?
Install piping weights or correct by hand if
any piping is in contact with other parts.
Is the fan in contact with other parts? If
so separate the fan from the other parts.
3
|
Troubleshooting
Possible to be checked
by DCS Residential
Yes
See details on the left.
No
Possible to be checked
by DCS Residential
No
Service manual
draft – 21/12/2023 13:09
43