Daikin Perfera ARXM25A Service Manual page 54

Table of Contents

Advertisement

4
|
Third party components
To check if the refrigerant circuit is clogged
Service manual
54
draft – 21/12/2023 13:09
2 Check if the stop valves are completely open.
The refrigerant circuit stop valves are
open?
Yes
No
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
1 Wait for the refrigerant to reach the outdoor temperature.
2 Check that all field piping is done according to the refrigeration practice and
installation manual:
▪ Correct piping diameters
▪ Piping distance limits are followed
▪ NO pipes are squeezed
▪ NO short radius bends
3 Connect a manometer to the service port.
4 Turn ON the power of the unit.
5 Activate Heating operation via the user interface.
6 Read the pressure on the pressure gauge. If, at the start of the unit operation,
the pressure is high or very low, the refrigerant circuit might be clogged.
7 On the refrigerant liquid piping (between the indoor unit heat exchanger and
the outdoor unit heat exchanger (coil)), using a contact thermometer,
measure the temperature before and after every restricting device. If a big
temperature difference is measured (>2.5~4K), an internal pipe obstruction
may be present at this location.
INFORMATION
Focus on positions with a potential risk for clogging such as:
Filters
Valves
Brazing points
...
INFORMATION
A bigger temperature drop before and after the expansion valve can be normal,
however excessive ice is indicating a malfunction of the expansion valve or internal
obstruction of the valve (dirt or ice build up in case of humidity in the system).
Temperature drop found?
Yes
Action
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Open the stop valves of the refrigerant
circuit, see
"4.2.2 Repair
4
procedures" [
 58].
Action
Replace the clogged part, see
"4.2.2 Repair
procedures" [
RXM20~50A + ARXM25~50A + FTXM20~50A + ATXM20~50A + CTXM15A
4
 58].
Split Perfera ZETA R32
ESIE23-06 – 2023.12