Refrigerant Piping At The Outdoor Unit; Insulating The Refrigerant Piping And Connections - Trane 17 Series Installer's Manual

Mini-split inverter system
Hide thumbs Also See for 17 Series:
Table of Contents

Advertisement

17 Series Mini-Split

Refrigerant Piping at the Outdoor Unit

Tighten the fl are nut of the connection pipe at the outdoor unit valve connector. Follow the fl are
nut guidelines in this manual.
Pipe Diameter in. (mm)
1/4" (6.35)
3/8" (9.52)
1/2" (12.7)
5/8" (15.9)
1. To prevent distortion and breaking of the pipe, bend the pipe with a radius of curvature of 6 in.
(150 mm) or more. Use a tubing bender when forming the copper tubing into a bend.
2. If the pipe is bent repeatedly at the same place, it will break.
Connect the gas pipe after connecting the liquid pipe completely.

Insulating the Refrigerant Piping and Connections

1. The refrigerant pipes should be insulated and wrapped with appropriate insulating material
and wrapping tape. Each interconnecting refrigeration line must be insulated individually
between the indoor and outdoor unit. The insulation must meet or exceed adopted codes
and standards from the AHJ. Additionally, the insulation joints and seams must be sealed.
Doing so will reduce external condensation formation and serve to prevent water leakage thus
reducing or eliminating water from leaking on building materials from the refrigeration lines.
Torque Reference Table
Tube Thickness in. (mm)
≥ 0.03 (0.8)
≥ 0.03 (0.8)
≥ 0.03 (0.8)
≥ 0.04 (1.0)
NOTICE
Tightening Torque
11.25 - 14.75 lb•ft (15 ~ 20 N•m)
22.25 - 29.50 lb•ft (30 ~ 40 N•m)
33.25 - 40.50 lb•ft (45 ~ 55 N•m)
44.25 - 47.75 lb•ft (60 ~ 65 N•m)
Caution