Hanging the Indoor Unit

Note: It is recommended the indoor unit be mounted on a non-porous fl at surface. Doing so will
reduce unfi ltered air from entering the unit as well as reduce sweating behind the unit. Ensure the
insulation sections surrounding the refrigeration and condensate pipes are sealed and without
cracks or openings.
1. Insert the bound pipes and wires into the wall sleeve and pass through to the outside.
2. Hang the indoor unit on the wall-mounting frame.
3. Seal any and all openings and gaps with sealant.
4. Secure the wall pipe bundle with saddles.
5. Ensure the indoor unit is securely and tightly installed to the wall.
6. Do not bend the drain hose excessively to prevent blockage.