17 Series Mini-Split
If the outdoor unit is installed higher
than the indoor unit:
1. Taping should be done from the lower to the
upper part. Do not wrap too tightly to avoid
compression of the insulation, otherwise its
eff ectiveness is reduced.
2. All pipes are bound and taped together and
also should be trapped to prevent water
from returning to the room.
3. Secure all pipes to the wall with saddles.
Note: Oil traps are sometimes needed when
the outdoor unit is installed higher than the
indoor unit. An oil trap is needed for each 20 ft.
(6m) of vertical rise on the gas pipe.

Installing the Refrigerant Piping

Installing the Refrigerant Piping
Flaring Process
Flaring Process
1. 1. Hold the pipe downward to prevent cuttings from entering the pipe.
Hold the pipe downward to prevent cuttings from entering the pipe.
ODU
Drain
Pipe
Oil Trap
Liquid
Pipe
Gas Pipe
Oil Trap
Oil Trap
Drain
Pipe
IDU