IMPORTANT: Do NOT change units equipped with the VFD
option to operate at less than the preset 66% minimum Hertz
(Hz) setting. For example, do not change a unit equipped with
a standard static motor to operate at less than 40 Hz (which is
66% of its 60 Hz rating).
Tables 2-9 list the minimum recommended cfm per fan
motor type (single speed or 2-speed) for the units covered
in this document.
Table 2 — 580J Min cfm Per Fan Motor Type
SINGLE SPEED
MODEL-SIZE
FAN MOTOR
580J*07
1800
580J*08
2250
580J*09
2550
580J*12
3000
580J*14
3600
580J*16
4500
580J*17
4500
580J*20
5250
580J*24
6000
580J*28
7500
580J*30
8250
Table 3 — 558J Min cfm Per Fan Motor Type
SINGLE SPEED
MODEL-SIZE
FAN MOTOR
558J*07
1800
558J*08
2250
558J*09
2550
558J*12
3000
558J*14
3600
558J*16
4500
558J*17
4500
558J*20
5250
558J*24
6000
558J*28
7500
558J*30
8250
Table 4 — 548J Min cfm Per Fan Motor Type
SINGLE SPEED
MODEL-SIZE
FAN MOTOR
548J*07
1800
548J*08
2250
548J*09
2550
548J*12
3000
548J*14
3750
548J*17
4500
548J*24
6000
2-SPEED FAN
2-SPEED FAN
MOTOR (AT
MOTOR (AT
HIGH SPEED)
LOW SPEED)
1800
1188
2250
1485
2873
1896
3380
2231
4225
2789
5625
3713
4500
2970
5250
3465
6000
3960
8450
5577
8250
5445
2-SPEED FAN
SPEED FAN
MOTOR (AT
MOTOR (AT
HIGH SPEED)
LOW SPEED)
1800
1188
2250
1485
2873
1896
3380
2231
4225
2789
5625
3713
4500
2970
5250
3465
6000
3960
8450
5577
8250
5445
2-SPEED FAN
2-SPEED FAN
MOTOR (AT
MOTOR (AT
HIGH SPEED)
LOW SPEED)
1800
1188
2535
1673
2873
1896
3000
1980
4225
2789
5070
3346
6760
4462
Table 5 — 581J Min cfm Per Fan Motor Type
SINGLE SPEED
MODEL-SIZE
FAN MOTOR
581J*07
1800
581J*08
2250
581J*09
2550
581J*11
3000
581J*12
3000
581J*14
3750
581J*17
4500
581J*20
5250
581J*24
6000
581J*28
7500
Table 6 — 551J Min cfm Per Fan Motor Type
SINGLE SPEED
MODEL-SIZE
FAN MOTOR
551J*07
1800
551J*08
2250
551J*09
2550
551J*11
3000
551J*12
3000
551J*14
3750
551J*17
4500
551J*20
5250
551J*24
6000
551J*28
7500
Table 7 — 549J Min cfm Per Fan Motor Type
SINGLE SPEED
MODEL-SIZE
FAN MOTOR
549J*07
1800
549J*08
2250
549J*09
2550
549J*12
3000
Table 8 — 524J***A Min cfm Per Fan Motor Type
SINGLE SPEED
MODEL-SIZE
FAN MOTOR
524J*07A
1800
524J*08A
2250
524J*12A
3000
524J*14A
3750
524J*16A
4500
524J*25A
6000
524J*28A
7500
524J*30A
9000
Table 9 — 524J***H Min cfm Per Fan Motor Type
SINGLE SPEED
MODEL-SIZE
FAN MOTOR
524J*07H
1800
524J*08H
2250
524J*12H
3000
524J*16H
4500
524J*25H
6000
4
2-SPEED FAN
2-SPEED FAN
MOTOR (AT
MOTOR (AT
HIGH SPEED)
LOW SPEED)
1800
1300
2535
1673
2550
1683
3380
2231
3380
2231
4225
2789
5070
3346
5915
3904
7500
4950
8450
5577
2-SPEED FAN
2-SPEED FAN
MOTOR (AT
MOTOR (AT
HIGH SPEED)
LOW SPEED)
1800
1200
2535
1673
2550
1683
3380
2231
3380
2231
4225
2789
5070
3346
5915
3904
7500
4950
8450
5577
2-SPEED FAN
2-SPEED FAN
MOTOR (AT
MOTOR (AT
HIGH SPEED)
LOW SPEED)
1800
1188
2250
1485
2873
1896
3380
2231
2-SPEED FAN
2-SPEED FAN
MOTOR (AT
MOTOR (AT
HIGH SPEED)
LOW SPEED)
2030
1338
2535
1673
3380
2231
4225
2789
4500
2970
6000
3960
8450
5577
9295
6135
2-SPEED FAN
2-SPEED FAN
MOTOR (AT
MOTOR (AT
HIGH SPEED)
LOW SPEED)
2030
1338
2535
1673
3380
2231
4500
2970
6000
3960