Bryant 580J Installation, Start-Up And Service Instructions Manual page 37

Variable frequency drive (vfd) factory-installed option 2-speed motor control for 2-stage cooling rooftop units
Hide thumbs Also See for 580J:
Table of Contents

Advertisement

Table 20 — ACS320 VFD Common Parameters for 524J Units with Electromechanical Controls
PARAMETERS
9802
9907
1001
1102
1103
1201
1202
1203
1204
1205
1401
1403
1501
1601
1608
1611
2007
2008
2101
2102
2201
2202
2203
2603
2606
3102
3103
3104
5101
5201
5202
5203
5301
5302
5303
5304
5305
LEGEND
— = HVAC Default, field does not require change.
DESCRIPTION
COMM PROT Sel
Motor Nominal Frequency
EXT1 Commands
EXT1/EXT2 Sel
REF 1 Select
Const Speed Sel
Const Speed 1
Const Speed 2
Const Speed 3
Const Speed 4
Relay Output 1
Relay Output 3
AO1 Content Sel
Run Enable
N/A
Parameter View
Minimum Frequency
Maximum Frequency
Start FCN
Stop FCN
ACCEL/DECEL
ACCEL
DECEL
IR COMP Volt
Switching Freq
Trial Time
Delay Time
AR Overcurrent
FBA Type
Station ID
Baud Rate
Parity
EFB Protocol ID
EFB Station ID
EFB Baud Rate
EFB Parity
EFB CTRL Profile
37
SETTING ACS320
60Hz
DI 2,3
40Hz
60Hz
60Hz
(16) FLT/ALARM
3
0.0 HZ
60HZ
(1) Auto
(1) Coast
(0) Not Sel
30s
30s
0 volts
4 KHz
300.0s
6.0s
(1) Enabled

Advertisement

Table of Contents
loading

This manual is also suitable for:

558j548j581j551j549j

Table of Contents