Table 22 — ACH550/580 VFD Common Parameters for 558J/580J and 551J/581J Units with Electromechanical Controls
PARAMETERS ACH550 / 580
9802 / 58.01
9907 / 99.08
1001 / 20.01
1102 / 19.11
1103 / 28.11
1201 / 28.22
1201 / 28.23
1202 / 28.26
1203 / 28.27
1204 / 28.28
1205 / 28.29
1401 / 10.24
1403 / 10.30
1501 / 13.12
1601 / 20.40
2007 / 30.13
2008 / 30.14
2101 / 21.19
2102 / 21.03
2201 / 28.71
2202 / 28.72
2203 / 28.73
2606 / 97.01
5101 / 51.01
5201 / 58.03
5202 / 58.04
5203 / 58.05
5301 / 58.25
5302 / 58.03
5303 / 58.04
5304 / 58.05
5305 / 58.25
DESCRIPTION
COMM PROT Sel
Motor Nominal Frequency
EXT1 Commands
EXT1/EXT2 Sel
REF 1 Select
Const Speed Sel
Const Speed Sel
Const Speed 1
Const Speed 2
Const Speed 3
Const Speed 4
Relay Output 1
Relay Output 3
AO1 Content Sel
Run Enable
Minimum Frequency
Maximum Frequency
Start FCN
Stop FCN
ACCEL/DECEL
ACCEL
DECEL
Switching Freq
FBA Type
Station ID
Baud Rate
Parity
EFB Protocol ID
EFB Station ID
EFB Baud Rate
EFB Parity
EFB CTRL Profile
39
SETTING ACH550 | ACH580
60Hz
DI2,3 | DI2
DI2,3 | DI3
40Hz
60Hz
60Hz
16 FLT/Alarm | FLT/ (14) Fault
0Hz
60Hz
Auto | Automatic
Ramp
Not Sel | 0
30s
30s
4kHz