Download Print this page

Viking MIRAGE VK462 Technical Data Manual page 7

Standard and qr concealed pendent sprinkler and hp sprinkler

Advertisement

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Sprinkler and
Adapter Assembly
• Protective cap
removed
• Use wrench
14047W/B**
Step 1:
Carefully slide the
wrench sideways around
the deflector and pins
NEVER install the sprinkler by applying the installation
wrench across the frame arms. DO NOT overtighten.
Use only the designated sprinkler wrenches, Viking
Part Numbers 14047W/B** or 14031**. A leak tight seal
should be achieved by turning the sprinkler clockwise
1 to 1-1/2 turns beyond finger tight.
1/2" (15 mm) NPT
NOTE: Upon sprinkler activation, the deflector descends
to approximately 13/16" (21 mm) below the sprinkler body.
Form No. F_103005
21.08.14
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Sprinkler Wrench
Part No. 14047W/B**
Figure 3: Sprinkler Installation and Proper Wrench Usage
**
A 1/2" ratchet is required (Not available from Viking)
2-9/16" (65 mm)
Maximum
Figure 4: Sprinkler Dimensions and Cover Installation
Rev 21.1
MIRAGE
®
QR CONCEALED PENDENT
SPRINKLER VK462 AND HP
SPRINKLER VK463 (K5.6)
Step 2:
Carefully press the wrench upward and
turn slightly to ensure engagement with
the sprinkler wrench flats.
Sprinkler
wrench flat
2-1/16" (52 mm)
Minimum
2-3/4" (70 mm) or
3-5/16" (84 mm)
Replaces Form No. F_103005 Rev 20.3
(Revised VdS Approval requirements.)
Page 7 of 7
STANDARD AND
2-1/4" (57 mm)
diameter opening
required in the
ceiling.
Sprinkler
frame arms

Advertisement

loading

This manual is also suitable for:

Mirage vk463