1. DESCRIPTION
Viking QR COIN
Sprinklers are quick response specific application sprinklers
®
for combustible interstitial (concealed) spaces (i.e., between floors, as well
as low pitch attics that meet the criteria shown in the figures in this data
page). These upright sprinklers are designed for use in specific light hazard
combustible, as well as non-combustible, concealed spaces requiring sprinkler
protection. The orifice design of the Viking QR COIN
K-factor of 5.6 (80 metric*), allows efficient use of available water supplies for
hydraulically designed fire protection systems. The glass bulb operating element
and special deflector combine speed of operation and area of coverage to meet
the crucial fire protection requirement for shallow space combustible concealed
spaces. The Electroless Nickel PTFE (ENT) coating has been investigated for
installation in corrosive environments and is listed/approved as indicated in the
Approval Charts.
FEATURES
In some cases COIN
concealed spaces of applications requiring sprinkler protection in open truss
construction of both wood and steel trusses (see Figure 3) and solid wood or
composite wood joist with upper deck filled with non-combustible insulation
(see Figure 5).
COIN
Sprinklers can also be installed with steel pipe in protected areas
®
constructed of solid wood joists (see Figure 7), and solid wood or composite
wood joist with upper deck filled with non-combustible insulation (see Figure 8),
and in unobstructed open truss construction of both wood and steel trusses
(see Figures 9 and 10) as well as obstructed wood truss construction (see
Figure 11).
When using steel pipe, COIN
using air or gas as a supervisory medium (see Figures 7–11).
In certain scenarios, draft curtains are NOT required when sprinkler spacing
meets either of the following criteria (also refer to Design Criteria):
- 14' X 14' (4,3 m X 4,3 m) for solid wood joists or trusses on edge
- 16' X 16' (4,9 m X 4,9 m) for truss construction on face (not on edge)
For examples of trusses on face or edge see Figures 13A and 13B.
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
Refer to the Approval Chart and Design Criteria in this technical data sheet for cULus Listing requirements that must be followed.
The COIN
Sprinkler has been tested to address the proper application density for shallow concealed combustible space fire
®
protection when installed in accordance with this technical data page. The COIN
as specified in the appropriate application described in Figures 3–12. The clearance from the sprinkler deflector to the roof is critical
to operation of the sprinkler (refer to Figures 3–12). The clearances from pipe to lower ceiling for CPVC pipe is critical for protection
of CPVC pipe.
For open truss and joist spaces, the maximum detection area is important for proper installation.
In certain installations, draft curtains or heat collection baffles or solid walls are required using wood or other product that
will not allow heat to escape. In these installations, the maximum detection space shall be limited to 1000 ft
2000 ft
(185 m
) for solid wood joists. The draft curtain is required to protrude down from the top deck surface as specified herein.
2
2
Additionally, draft curtains are not required and the maximum detection space shall be unlimited for open truss construction with
the top chord member on their face (not on edge) when sprinkler spacing is up to 16' X 16' (4,9 m X 4,9 m) and for solid wood
joists or trusses on edge when sprinkler spacing is up to 14' X 14' (4,3 m X 4,3 m). In these cases, draft curtains are not required.
Form No. F_081216
21.03.06 Rev 20.3
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Sprinklers can allow the use of CPVC piping within the
®
Sprinklers can be applied as a dry system
®
Sprinkler, with a nominal
®
®
COIN
QUICK
®
RESPONSE UPRIGHT
SPRINKLER VK950
(SPECIFIC APPLICATION)
COIN
Sprinkler
®
VK950
5.6K (80 metric)
Sprinkler must be installed in the upright position
Replaces Form No. F_081216 20.2
(Added new Figure 6 and 12.)
1 of 14
(93 m
) or
2
2

Advertisement

loading

Summary of Contents for Viking VK950

  • Page 1 (SPECIFIC APPLICATION) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com 1. DESCRIPTION Viking QR COIN Sprinklers are quick response specific application sprinklers ®...
  • Page 2 Sprinkler is available through a network of domestic and international distributors. See The Viking ® Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking’s current list price schedule or contact Viking directly. 1-3/4” (45 mm) Protective clip Wrench Flat 2-1/4”...
  • Page 3 Corrosion-Resistant Coating: Example: 20757AE = VK950 with Brass Finish and 200 °F (93 °C) Nominal temperature rating. This sprinkler is to be installed into an area with a maximum ambient temperature of 150 °F (65 °C) meaning if the area will experience temperatures above the maximum ambient rating, you shall use a higher temperature-rated sprinkler.
  • Page 4 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com DESIGN CRITERI A - CPVC PIPE (See Figures 3-6) (Also refer to the Approval Chart on page 3.)
  • Page 5 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com DESIGN CRITERI A - CPVC PIPE...
  • Page 6 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Figure 3: Open Wood Truss and Open Web Steel Joist Construction...
  • Page 7 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Figure 5: Solid Wood or Composite Wood Joist Construction with Non-Combustible Insulation...
  • Page 8 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com DESIGN CRITERI A - STEEL PIPE (See Figures 7 –...
  • Page 9 F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
  • Page 10 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Figure 8: Solid Wood or Composite Wood Joist Construction...
  • Page 11 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Figure 10: Open Wood Truss and Open Web Steel Joist Construction with Non-Combustible Insulation Filling to...
  • Page 12 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Figure 12: Wood Truss Construction with Chords on Face and Non-combustible Insulation Provided to the Bottom of the Trusses (CPVC and Steel Pipe, Cross Section View) Form No.
  • Page 13 (SPECIFIC APPLICATION) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com On Face 3-1/2" (89 mm) 1-1/2"...
  • Page 14: Technical Data

    • All obstruction criteria for extended coverage sprinklers per NFPA 13 shall apply unless specified differently in this data sheet. • For installations where the VK950 is installed up to a 15’-0” X 15’-0” spacing or less between sprinkler, the obstruction rules for standard coverage sprinklers shall apply.
  • Page 15: Listings And Approvals

    STANDARD RESPONSE, QUICK RESPONSE, EXTENDED COVERAGE, AND DRY SPRINKLERS Viking thermosensitive spray sprinklers consist of a small frame and either a glass bulb or a fusible operating element. Available styles include pendent, flush pendent, concealed pendent, upright, horizontal sidewall, vertical sidewall, or conventional, depending on the particular sprinkler model selected.
  • Page 16 C. Installation Instructions - Dry Sprinklers WARNING: Viking dry sprinklers are to be installed in the 1” outlet (for dry and preaction systems), or run of malleable, ductile iron, or Nibco CPVC* threaded tee fittings (for wet systems) that meet the dimensional requirements of ANSI B16.3 (Class 150), or cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16.4 (Class 125), even at branch line ends.
  • Page 17: Operation

    4. After installation, the entire sprinkler system must be tested. The test must be conducted to comply with the installation stand- ards. Viking high pressure sprinklers may be hydrostatically tested at a maximum of 300 psi (20.7 bar) for limited periods of time (two hours), for the purpose of acceptance by the Authority Having Jurisdiction.
  • Page 18 Refer to the Authority Having Jurisdiction for minimum replacement requirements. 7. AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
  • Page 19 1. DESCRIPTION Viking fire sprinklers consist of a threaded frame with a specific waterway or orifice size and a deflector for distributing water in a specified pattern. A closed or sealed sprinkler refers to a complete assembly, including the thermosensitive operating element. An open sprinkler does not use an operating element and is open at all times.
  • Page 20 TECHNICAL DATA SPRINKLER OVERVIEW The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com VERTICAL SIDEWALL (VSW) SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The deflector provides a water spray pattern outward in a quarter-spherical pattern and can be installed in the upright or pendent position with the flow arrow in the direction of discharge.
  • Page 21 Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
  • Page 22 Refer to the appropriate technical data page and NFPA standards for complete care, handling, installation, and maintenance instructions. For additional product and system information Viking data pages and installation instructions are available on the Viking Web site at www.vikinggroupinc.com.
  • Page 23 * Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www. vikinggroupinc.com.
  • Page 24 • while ceiling finish work is being completed. Use only the designated Viking recessed sprinkler wrench (refer to the appropriate sprinkler data page) to install these sprinklers. NOTE: The protective cap is • temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed.
  • Page 25 Take care not to crack the wax coating on the units. • For touching up the wax coating after installation, wax is available from Viking in bar form. Refer to Table 1 below. The coating MUST be repaired after •...
  • Page 26: Warranty Terms And Conditions

    For more information, go to www.P65Warnings.ca.gov 2. WARRANTY TERMS AND CONDITIONS For details of warranty, refer to Viking’s current list price schedule at www.vikinggroupinc.com or contact Viking directly. New Bulletin Form No. F_111218 18.11.15...