①
Insert plate
②
Mounting plate
③
Cover
④
Rear panel
⑤
Air discharge
⑥
Air inlet - filter with filter fan
⑦
To maintain the degree of protection IP54, the surfaces
well as between the mounting plate and insert plate must be sealed all around. (for example, sealant Terostat-91
from the Teroson company)
Figure 4-101 Example 2: mounting in the cabinet with mounting plate
It is recommended that you attach a cover and filter fan to the cabinet.
The filtered fan must be fitted in such a way that the cooling air required by the drive line-up
is not restricted. The overall cooling air requirement is obtained from the sum of the
individual components (see Section "Technical data").
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
4.9 Smart Line Modules with external air cooling
⑦
between the mounting plate and the cabinet strip as
Line Modules Booksize
323