Siemens 6SL3120-2TE21-0AA3 Manual page 324

Booksize power units
Table of Contents

Advertisement

Insert plate
Mounting plate
Cover
Rear panel
Air discharge
Air inlet - filter with filter fan
To maintain the degree of protection IP54, the surfaces
well as between the mounting plate and insert plate must be sealed all around. (for example, sealant Terostat-91
from the Teroson company)
Figure 4-101 Example 2: mounting in the cabinet with mounting plate
It is recommended that you attach a cover and filter fan to the cabinet.
The filtered fan must be fitted in such a way that the cooling air required by the drive line-up
is not restricted. The overall cooling air requirement is obtained from the sum of the
individual components (see Section "Technical data").
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
4.9 Smart Line Modules with external air cooling
between the mounting plate and the cabinet strip as
Line Modules Booksize