A-13
S1 DIP Switch Bank on Control Box Motherboard (For software version S24456)
Switch
Off
1
Standard speed gearbox limits adjustable
2
WFS Display = inches/minute
3
Left Display is always preset WFS
CC modes override this switch regardless of position. Left Display is always preset weld cur-
rent when weld current is not flowing and actual weld current when weld current is flowing
4
Run-in = Minimum Speed Available
If any option containing a Run-in setting is connected to the motherboard, it automatically
overrides this switch regardless of position.
5
Memory change with trigger disabled
6
Acceleration, MSB (Sets acceleration rate for wire drive) see below
7
Acceleration
8
Acceleration, LSB
Note: the factory shipped settings for the S1 switches are as follows:
PF-10 (and Dual) Domestic - All switches "OFF"
PF-11 Domestic - switches 2-8 "OFF", 1 "ON"
S2 DIP Switch Bank on Control Box Motherboard (For software version S24456)
Switch
Off
1
Network Group ID, MSB (Assigns Control Box to a specific group) (Off is factory setting)
2
Network Group ID, LSB (Assigns Control Box to a specific group ) (Off is factory setting)
3
4-Step Domestic Configuration
4
Power Feed 10 / Dual
5
Procedure Change with Trigger "OFF"
6
Set lower limits
7
Set upper limits
8
Must be on for all units (Permits selection of extended modes)
Note: the factory shipped settings for the S2 switches are as follows:
PF-10 (and Dual) Domestic - switches 1-7 "OFF", 8 "ON"
PF-11 Domestic - switches 1-3,5-7 "OFF", 4,8 "ON"
MSB - Most Significant Bit or Byte. This is the bit in a binary number or DIP switch bank that is furthest to the left.
LSB - Least Significant Bit or Byte. This is the bit in a binary number or DIP switch bank that is furthest to the right.
INSTALLATION
On
High speed gearbox limits adjustable
WFS Display = meters/minute
Left Display is preset WFS when weld current is not flowing
Left Display is actual weld current when weld current is flowing
Run-in = weld WFS
Memory change with trigger enabled
(Sets acceleration rate for wire drive) see below
(Sets acceleration rate for wire drive) see below
PF-10 (and Dual) European - switches 1 & 3-8 "OFF", 2 "ON"
PF-11 European - switches 3-8 "OFF", 1,2 "ON"
On
4-Step European Configuration
Power Feed 11
Procedure Change with Trigger "ON"
PF-10 (and Dual) European - switches 1,2,4-7 "OFF", 3,8 "ON"
PF-11 European - switches 1,2,5-7 "OFF", 3,4,8 "ON"
POWER WAVE 455/POWER FEED 10
A-13