Connecting The Cable Shield - Siemens SINAMICS S220 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S220:
Table of Contents

Advertisement

3. Cut out the detachable tabs at the motor connection block if the cables have a diameter
higher than 9.5 mm (0.37 inch).
4. Place the cable lug onto the threaded studs.
5. Screw the nuts onto the threaded studs and tighten them. Socket wrench size 10. Tightening
torque: 6 Nm (53.1 lbf in)
6. Close the motor connection block cover.
7. Insert the connector for the holding brake into interface X11 provided on the lower side of
the component.
8. When required, in the threaded socket M4 on the component, fasten a shield connection
clamp, type KLBUE 3-8 SC (Weidmüller), and connect the shield of the holding brake there.
8.4.11.5

Connecting the cable shield

Overview
You can fasten the shield of the motor connection cable to the shield connection plate of the
Motor Module using a hose clamp or a shield connection clamp.
Requirement
The following requirements must be satisfied:
• The motor connection cable is connected at the motor connection block.
• The shield connection plate is mounted.
• Use a suitable hose clamp or shield connection clamp.
Shield connection clamp
Phoenix SK 14
Phoenix SK 35
Booksize power units
Equipment Manual, 09/2023, A5E53307519B AA
Use
For shielded single cores with a conductor diame‐
ter of up to 14 mm (0.55 inch)
For shielded cables with a cable diameter of up to
35 mm (1.38 inch)
Motor Modules
8.4 Motor Modules 45 A and 60 A
Article number
8WH9130-0MA00
8WH9130-0PA00
207