Siemens Synco-Gamma Application Manual
Siemens Synco-Gamma Application Manual

Siemens Synco-Gamma Application Manual

Hotel buildings

Advertisement

Quick Links

Synco-Gamma
Application Guide
Hotel buildings
www.siemens.com/bt /integrated-applications

Advertisement

loading

Summary of Contents for Siemens Synco-Gamma

  • Page 1 Synco-Gamma Application Guide Hotel buildings www.siemens.com/bt /integrated-applications...
  • Page 3 VAV plant with a host of products from Siemens’ KNX range: From simple solutions with fan coil units including switching of electric circuits to VAV sys- tems for larger rooms with automatic lighting and blind control.
  • Page 4 Summary Functions Benefits Page Efficiency class Fan coil unit, radiator, lighting, sun protection (hotel room) Heating and cooling, 1 control loop: Individual room temperature control and automatic data ex- · Automatic or manual fan control, 1- or 3- change with primary plant together save up to 30% heat- speed ing/cooling energy.
  • Page 5 Efficiency class Fan coil unit, radiator, lighting, sun protection (hotel room) Heating and cooling, 2 control loops: · Individual room temperature control and automatic data exchange Individual room temperature control, heating with primary plant together save up to 30% heating/cooling energy. and cooling ·...
  • Page 6 Efficiency class Fan coil unit, radiator, lighting (hotel room) Heating and cooling, 1 control loop: Individual room temperature control and automatic data exchange · Individual room temperature control, heating with primary plant together save up to 30% heating/cooling energy. and cooling ·...
  • Page 7 Efficiency class Air conditioning plant, indoor air quality con- trol, lighting (reception area) Heating and cooling, indoor air quality control · Temperature control and automatic data exchange Room-supply air temperature control/CO control with primary plant together save up to 30% heat- ·...
  • Page 8 Efficiency class VAV plant, indoor air quality control, lighting, sun protection (fitness room) Heating and cooling, indoor air quality control · Temperature control and automatic data exchange with Fully integrated VAV application with temperature, CO primary plant together save up to 30% heating/cooling and volumetric air flow control energy.
  • Page 9 Scenarios for hotel rooms For hotel rooms, the following usage scenarios are considered realistic: HVAC A typical HVAC scenario could look as follows: When a room is not occupied, it operates continuously in Economy mode. The moment the guest checks in, the hotel reservation system switches the room’s operating mode from Economy to Precomfort.
  • Page 10 Hotel-specific functions The functions described below are used primarily in hotels: Alarm function The alarm function can be triggered via pushbutton. When pressed, a signal is sent to the management station. The alarm can be visualized on a suitable display unit (touch panel or webbrowser) or on a panel with signal lamp.
  • Page 11 Application Manual Nr. 01 Synco™ Hotel rooms – room automation & Gamma Fan coil unit with radiator in the bathroom, sun protection, presence- dependent switching off of lighting and power supply Features · Individual room temperature control, heating and cooling ·...
  • Page 12 Application Manual Nr. 01 Synco™ Hotel rooms – room automation & Gamma EnOcean window contact (3rd party product): The window contact causes the room operating mode to switch to Economy when the window is open. EnOcean hotel card switch (3rd party product): When the card is inserted, the hotel card switch causes the room operating mode to change from Precomfort to Comfort.
  • Page 13 Application Manual Nr. 01 Synco™ Hotel rooms – room automation & Gamma 2-pipe fan coil unit with radiator HVAC control · Heating or cooling · On/off, PWM or 3-position control of heating/cooling and radiator actuators · Automatic or manual fan control, 1- or 3-speed ·...
  • Page 14 Application Manual Nr. 01 Synco™ Hotel rooms – room automation & Gamma Function Description of functions description Individual room temperature control Blinds control The room thermostat (RDF) acquires the temperature, The weather station (AP257/32) with its built-in GPS controls it via the fan coil unit and calculates the receiver measures solar radiation and controls shad- demand for heat or cooling energy.
  • Page 15 & Gamma Secondary The Application Sheets listed below describe individual controller applications and contain detailed information. documents They can be downloaded from the Internet at www.siemens.com/hit Application no. Name of application Product no. Synco Application Sheet, 2-pipe fan coil unit with radiator...
  • Page 16 Application Manual Nr. 02 Synco™ Hotel rooms – room automation & Gamma Fan coil unit with radiator in the bathroom, sun protection, presence- dependent switching off of lighting and power supply Features · Individual room temperature control, heating and cooling ·...
  • Page 17 Application Manual Nr. 02 Synco™ Hotel rooms – room automation & Gamma 250 VA. RL 521/23 blind actuator: The RL 521/23 features 2 relay contacts to control blinds. RS 510/23 binary output, 2-fold: The RS 510/23 features 2relay contacts to switch electric circuits. RXZ97.1 gateway EnOcean/KNX: The RXZ97.1 converts EnOcean wireless signals from the wall transmitter to KNX telegrams.
  • Page 18 Application Manual Nr. 02 Synco™ Hotel rooms – room automation & Gamma Variants Product no. and description Stock number AP 118 automation module box 5WG1 118-4AB01 UP 525/13 universal dimmer, 1 x 250 W 5WG1 525-2AB13 UP 520/13 blind actuator, 1 x 6 A 5WG1 520-2AB13 UP 510/13 binary output , 2 x 10 A 5WG1 510-2AB13...
  • Page 19 Application Manual Nr. 02 Synco™ Hotel rooms – room automation & Gamma Function Description of functions description Individual room temperature control Blinds control The room unit (QAX) acquires the temperature and The weather station (AP257/32) with its built-in GPS makes it available to the room controller (RXB) which receiver measures solar radiation and controls shad- controls the fan coil unit and calculates the demand ing to protect the façade against sunlight.
  • Page 20 & Gamma Secondary The Application Sheets listed below describe individual controller applications and contain detailed information. documents They can be downloaded from the Internet at www.siemens.com/hit Application no. Name of application Product no. Synco Application Sheet, 4-pipe fan coil unit RXB21.1...
  • Page 21 Application Manual Nr. 03 Synco™ Hotel rooms – room automation & Gamma Fan coil unit with radiator in the bathroom, sun protection, presence- dependent switching off of lighting and power supply Features · Individual room temperature control, heating and cooling ·...
  • Page 22 Application Manual Nr. 03 Synco™ Hotel rooms – room automation & Gamma N 512/11 switching actuator, main module: The N 512/11 features 3 potentialfree relay contacts to control lighting groups and electric circuits. N 523/02 blind actuator: The N 523/02 features 4 channels to control up to 4 blind motors. UP 222/2 pushbutton, 2-fold, neutral: The UP 222/2 is used to control the lighting and/or the shad- ing.
  • Page 23 Application Manual Nr. 03 Synco™ Hotel rooms – room automation & Gamma Optional Product no. and description Stock number RMB795B central control unit S55370-C162…C167 OZW772.x webserver OZW772.x N 125/12 power supply 5WG1 125-1AB12 AP 257/32 weather station 5WG1 257-3AB32 N 151 IP viewer 5WG1 151-1AB01 UP 588 color touch panel 5WG1 588-2AB13...
  • Page 24 Application Manual Nr. 03 Synco™ Hotel rooms – room automation & Gamma When a room is not booked (or, if desired, when the guest is absent), a weather station outside the building protects up to 4 façades from extreme sunlight in the summer. This function helps to keep the rooms cool. The weather station also protects the blinds from damage caused by strong winds or other natural influences.
  • Page 25 & Gamma Secondary The Application Sheets listed below describe individual controller applications and contain detailed information. documents They can be downloaded from the Internet at www.siemens.com/hit Application no. Name of application Product no. Synco Application Sheet, 4-pipe fan coil unit RXB21.1...
  • Page 26: Application Manual

    Application Manual Nr. 04 Synco™ Hotel rooms – room automation & Gamma Fan coil unit with radiator in the bathroom, sun protection, presence- dependent switching off of lighting and power supply Features · Individual room temperature control, heating and cooling ·...
  • Page 27 Application Manual Nr. 04 Synco™ Hotel rooms – room automation & Gamma N 502/02 combi switching actuator: The N 502/02 features 8 inputs and 8 relay contacts. It is used to switch electric circuits and lighting groups and serves the pushbuttons as a KNX interface. N 523/02 blind actuator: The N 523/02 features 4 channels to control up to 4 blind motors.
  • Page 28 Application Manual Nr. 04 Synco™ Hotel rooms – room automation & Gamma Variants Product no. and description Stock number RDF600KN room thermostat S55770-T293 + UP 220/21 I/O pushbutton interface, 2 inputs/outputs 5WG1 220-2AB21 UP 525/13 universal dimmer, 1 x 250 W 5WG1 525-2AB13 UP 510/13 binary output, 2 x 10 A 5WG1 510-2AB13...
  • Page 29 Application Manual Nr. 04 Synco™ Hotel rooms – room automation & Gamma Function Description of functions description Individual room temperature control Blinds control The room thermostat (RDG) acquires the tempera- The weather station (AP257/32) with its built-in GPS ture, controls it via the fan coil unit and calculates the receiver measures solar radiation and controls shad- demand for heat or cooling energy.
  • Page 30 & Gamma Secondary The Application Sheets listed below describe individual controller applications and contain detailed information. documents They can be downloaded from the Internet at www.siemens.com/hit Application no. Name of application Product no. Synco Application Sheet, 2-pipe fan coil unit with radiator...
  • Page 31 Application Manual Nr. 05 Synco™ Hotel rooms – room automation & Gamma Fan coil unit with radiator in the bathroom, sun protection, presence- dependent switching off of lighting and power supply Features · Individual room temperature control, heating and cooling ·...
  • Page 32 Application Manual Nr. 05 Synco™ Hotel rooms – room automation & Gamma DELTA pushbutton, 2-fold, with labeling field (MUR, DND): One of the pushbuttons can be used to activate signal lamp DND (Do not disturb) outside and inside the room. The other pushbutton is used to activate the MUR function (Make up room).
  • Page 33 Application Manual Nr. 05 Synco™ Hotel rooms – room automation & Gamma 2-pipe fan coil unit with radiator HVAC control · Heating or cooling · On/off, PWM or 3-position control of heating/cooling and radia- tor actuators · Automatic or manual fan control, 1- or 3-speed ·...
  • Page 34 Secondary The Application Sheets listed below describe individual controller applications and contain detailed information. documents They can be downloaded from the Internet at www.siemens.com/hit Application no. Name of application Product no. Synco Application Sheet, 2-pipe fan coil unit with radiator...
  • Page 35 Application Manual Nr. 06 Synco™ Hotel rooms – room automation & Gamma Radiator in the room and the bathroom, sun protection, presence- dependent switching off of lighting and power supply Features · Individual room temperature control, heating · Two control loops for the room and the bathroom ·...
  • Page 36 Application Manual Nr. 06 Synco™ Hotel rooms – room automation & Gamma 10. DELTA pushbutton with "Bell" symbol (SOS): The pushbutton is connected to the UP 220 and is used to trigger the alarm function. 11. DELTA pushbutton, 2-fold, with labeling field (MUR, DND): One of the pushbuttons can be used to ac- tivate signal lamp DND (Do not disturb) outside and inside the room.
  • Page 37 Application Manual Nr. 06 Synco™ Hotel rooms – room automation & Gamma Room HVAC control Radiator heating · Heating · Setpoint shift · On/of, PWM or 3-position control of radiator/floor heat- ing system valves The temperature in every room is acquired and controlled. During nonoccupancy times (rooms not booked), the room temperatures are automatically lowered via the integrated hotel booking system.
  • Page 38 Secondary The Application Sheets listed below describe individual controller applications and contain detailed information. documents They can be downloaded from the Internet at www.siemens.com/hit Application no. Name of application Product no. Gamma Application Sheet,...
  • Page 39 Application Manual Nr. 07 Synco™ Hotel rooms – room automation & Gamma Floor heating in the room and the bathroom, sun protection, presence- dependent switching off of lighting and power supply Features · Individual room temperature control, heating · 2 control loops for the room and the bathroom ·...
  • Page 40 Application Manual Nr. 07 Synco™ Hotel rooms – room automation & Gamma DELTA pushbutton: The pushbutton can be connected to the KNX interface of the AQR and is used to control the lighting. 10. DELTA pushbutton with "Bell" symbol (SOS): The pushbutton is used to trigger the alarm func- tion.
  • Page 41 Application Manual Nr. 07 Synco™ Hotel rooms – room automation & Gamma Room HVAC control Radiator heating · Heating · Setpoint shift · On/off, PWM or 3-position control of radiator/floor heat- ing system valves Lighting control When the room is no longer occupied, the lighting is automatically switched off after a delay time. Blinds control The weather station (AP257/32) with its built-in GPS receiver measures solar radiation and controls shading to protect the façade against sunlight.
  • Page 42 Secondary The Application Sheets listed below describe individual controller applications and contain detailed information. documents They can be downloaded from the Internet at www.siemens.com/hit Application no. Name of application Product no. Gamma ApplicationSheet,...
  • Page 43 Application Manual Nr. 08 Synco™ Reception area – room automation & Gamma Air conditioning plant with indoor air quality and lighting control Features · Room-supply air temperature control/CO control · Automatic data exchange between room HVAC and primary plant · VAV controller to optimize the ventilation system ·...
  • Page 44 Application Manual Nr. 08 Synco™ Reception area – room automation & Gamma Device list Product no. and description Stock number AQR2576 room sensor, basic module with CO S55720-S203…206 AQR2532 room sensor, temperature S55720-S136 N 141/02 KNX/DALI gateway 5WG1 141-1AB02 UP258E21 presence detector with constant light control 5WG1 258-2EB21 UP 588 color touch panel 5WG1 588-2AB13...
  • Page 45 Application Manual Nr. 08 Synco™ Reception area – room automation & Gamma Lighting control Presence detectors (hotel card switches) help save energy by automatically switching the lighting off when the room is not occupied. A brightness sensor incorporated in the presence detector helps when switching and dimming lights, ensuring that the room is always optimally illuminated, using as little as possible artificial light.
  • Page 46 & Gamma Secondary The Application Sheets listed below describe individual controller applications and contain detailed information. documents They can be downloaded from the Internet at www.siemens.com/hit Application no. Name of application Product no. Synco Application Sheet, Room-supply air temperature cascade control with plate...
  • Page 47 Application Manual Nr. 09 Synco™ Restaurant area – room automation & Gamma VAV plant with indoor air quality and DALI constant light control Features · Fully integrated VAV application with temperature, CO , and volumetric air flow control · Automatic data exchange between room HVAC and primary plant ·...
  • Page 48 Application Manual Nr. 09 Synco™ Restaurant area – room automation & Gamma STA23 electrothermal actuator: The STA23 adjusts the valve according to the positioning signal it receives from the controller. UP 588 color touch panel: The UP 588 is used to control and monitor HVAC, the lighting and the blinds. Device list Product no.
  • Page 49 Application Manual Nr. 09 Synco™ Restaurant area – room automation & Gamma Room HVAC control VAV plant · Heating or cooling · (B1) DC 0...10 V or 3-position control of VAV boxes or (B1) damper actuators · Automatic or manual changeover of heating/cooling mode ·...
  • Page 50 Application Manual Nr. 09 Synco™ Restaurant area – room automation & Gamma Blinds control A weather station outside the building protects up to 8 façades from extreme solar radiation in the summer. This function helps to keep the rooms cool. The weather station also protects the blinds from damage caused by strong winds or other natural influences and controls them at dusk and according to temperatures to save heating energy during winter nights.
  • Page 51 Application Manual Nr. 09 Synco™ Restaurant area – room automation & Gamma Function Description of functions description Individual room temperature control Offset adjustments allow the configuration of constant light control with only one presence detector. Manual The room thermostat (RDU/RDG) acquires the tem- switching and dimming is made possible via the perature and controls valve actuator STA23 of the pushbutton.
  • Page 52 Room occupancy Secondary The Application Sheets listed below describe individual controller applications and contain detailed information. documents They can be downloaded from the Internet at www.siemens.com/hit Application no. Name of application Product no. Synco Application Sheet, VAV plant, single duct...
  • Page 53 Application Manual Nr. 10 Synco™ Fitness room – room automation & Gamma VAV plant with indoor air quality and DALI constant light control Features · Fully integrated VAV application with temperature, CO , and volumetric air flow control · Automatic data exchange between room HVAC and primary plant ·...
  • Page 54 Application Manual Nr. 10 Synco™ Fitness room – room automation & Gamma DELTA pushbutton: The pushbutton with DELTA bus coupling unit is used to control the lighting and/or the blinds. 10. DELTA pushbutton: The pushbutton is connected to the KNX interface of the AQR and is used to control the lighting and/or the blinds.
  • Page 55 Application Manual Nr. 10 Synco™ Fitness room – room automation & Gamma Room HVAC control VAV plant · Heating or cooling · (B1) DC 0...10 V or 3-position control of VAV boxes or (B1) damper actuators · Automatic or manual changeover of heating/cooling mode ·...
  • Page 56 Application Manual Nr. 10 Synco™ Fitness room – room automation & Gamma A weather station outside the building protects up to 8 façades from extreme solar radiation in the summer. This function helps to keep the rooms cool. The weather station also protects the blinds from damage caused by strong winds or other natural influences and controls them at dusk and according to temperatures to save heating energy during winter nights.
  • Page 57 Secondary The Application Sheets listed below describe individual controller applications and contain detailed information. documents They can be downloaded from the Internet at www.siemens.com/hit Application no. Name of application Product no. Synco Application Sheet, VAV plant, single duct...
  • Page 58 Application Manual Nr. 11 Synco™ Energy center – primary control & Gamma Heat, refrigeration and air handling Features · Demand-compensated production of heat, cooling energy, and supply air · Setpoint compensation depending on demand and outside temperature · Together with room automation: Prerequisite to attain efficiency class A conforming to EN 15232 Room setup RMH760B heating controller: The RMH760B controls the heating plant depending on the heat request...
  • Page 59 Application Manual Nr. 11 Synco™ Eenergy center – primary control & Gamma Ventilation control Supply air temperature control for VAV systems · Control of speed-controlled fans with differential pres- sure control · Control of air dampers depending on indoor air quality ·...
  • Page 60 Application Manual Nr. 11 Synco™ Energy center – primary control & Gamma refrigeration machine can be switched on only if water passes through the evaporator and the condenser The temperature is acquired in every room and controlled via the supply air, the radiator and the floor heating sys- tem.
  • Page 61 & Gamma Secondary The Application Sheets listed below describe individual controller applications and contain detailed information. documents They can be downloaded from the Internet at www.siemens.com/hit Application no. Name of application Product no. Synco - Application Guide Combination of the devices to a system RMU730B, …...
  • Page 63 In addition, we need to increase comfort for the well-being of users. Also, our need for safety and security is constantly growing. For our customers, success is defined by how well they manage these challenges. Siemens has the answers. www.siemens.com/synco...