Connecting
5.2 Connecting the sensor
Cable specifications
• Only use cables with at least the same degree of protection as the sensor to install the sensor.
• The line length from the cable gland to the terminals must be kept as short as possible. Line
loops in the terminal box must be avoided.
• To guarantee the IP67 degree of protection, use cables with the required specifications.
See also
Cable data (Page 48)
5.2

Connecting the sensor

Before you start
• Read the Safety notes (Page 9)
• Read the Basic safety notes: Installing/mounting
• Read the Basic safety notes: Connecting
28
WARNING
Protective conductor terminal
The required cable is min. AGW16 or 1.5 mm
WARNING
Wire insulation
For field wiring installation: Ensure that the national requirements of the country in which
the flowmeters are installed is met.
Cu.
2