Antifrost – All Models
0
When the temperature sensor is lower than 41
F:
•The 2-way valve will shift to the middle position
•The pump will start and the burner will operate at minimum power.
•The burner will shut off when the temperature sensor reaches 59
0
F.
•The pump will complete post circulation.