Controller Configuration Mode: (Use Figure 7-6 with Controller Parameters.)
Hold the Select button:
Now release the Select button.
Press:
or
or
or
Now either save your settings or enter the Advanced Configuration Mode to
set the engine data inputs, battery voltage, and communications.
Press:
or
or
Note: Shaded boxes show which number in the controller display changes when the up or down arrow
key is pressed. "x" denotes any number from 0 to 9.
Figure 7-8 Configuration Mode (system voltage/frequency, unit configuration, and engine type parameters)
42
Section 7 Controller
Move the generator set master switch to the RUN
position. (The generator set engine will not start.)
Wait about 5 seconds until the display shows the
program version number. (The number may be
different than the one shown here.)
Press the down arrow key and then the up arrow
key 3 times to enter the configuration mode.
(This is the controller "password.")
To set the voltage/frequency setting.
See Figure 7-6.
To step to the next parameter, unit configuration
Uc.
To set the unit configuration setting to Uc02, if
necessary.
To step to the next parameter, engine type Ec.
To set the engine type, if necessary.
To step to the next parameter, advanced
configuration mode or save mode selection.
To enter advanced configuration mode.
Go to Figure 7-9.
To proceed to the save mode without
entering the advanced configuration mode.
Go to Figure 7-10.
Display:
.
0
u
1 0 4
U u 0 x
U u 0 x
U c 0 2
E c 0 x
A d n c
E d 0 x
S A V E
TP-6359 7/08