Riello RLS 300/BP MX Installation, Use And Maintenance Instructions page 36

Dual fuel kerosene and gas oil/ gas burners
Hide thumbs Also See for RLS 300/BP MX:
Table of Contents

Advertisement

Pump
The delivery pressure must be stable. The depression must be
less than 0.4 bar. Unusual noise must not be evident during pump
operation.
If the pressure is found to be unstable or if the pump runs noisily,
the flexible hose must be detached from the line filter and the fuel
must be sucked from a tank located near the burner. This meas-
ure permits the cause of the anomaly to be traced to either the
suction piping or the pump.
If the pump is found to be responsible, check to make sure that
the filter is not dirty. The vacuometer is installed upstream from
the filter and consequently will not indicate whether the filter is
clogged or not. Contrarily, if the problem lies in the suction line,
check to make sure that the filter is clean and that air is not enter-
ing the piping.
Please check that the supply line and filters are clear. The use of
a pump vacuum gauge will assist in this. This measure permits
the cause of the anomaly to be traced to either the suction line or
the pump.
If the problem lies in the suction line, check to make sure that the
filter is clean and that air is not entering the piping.
Hoses
 Check periodically the flexible pipes conditions. They have
to be replaced at least every 2 years.
 In case of use of gas oil and bio fuel blends, it is strongly rec-
ommended to inspect even more frequently the hoses and
replace them where contamination has occurred.
 Check to make sure that the hoses are still in good condi-
tion.
Nozzles
Do not clean the nozzle openings; do not even open them.
The nozzle filters however may be cleaned or replaced as re-
quired.
It is advisable to replace nozzles every year during regular main-
tenance operations.
Combustion must be checked after the nozzles have been
changed.
Fuel tank
If water or contamination is present within the fuel tank, it is es-
sential that this is removed before the equipment is to be used.
This is extremely important when gas oil containing Bio diesel is
in use. If in doubt about how to achieve this then please contact
the fuel or oil tank supplier.
Combustion
In case the combustion values found at the beginning of the inter-
vention do not respect the standards in force or, in any case, do
not correspond to a proper combustion, contact the Technical
Assistant and have him carry out the necessary adjustments.
EN 267
Calibration CO
Theoretical max. CO
2
0 % O
2
15.2
20036762
Excess air
Max output
Min output
  1.2
  1.3
%
CO
2
 = 1,2
 = 1,3
mg/kWh
 100
12.6
11.5
Maintenance
Gas leaks
Make sure that there are no gas leaks on the pipework between
the gas meter and the burner.
Gas filter
Change the gas filter when it is dirty.
Combustion
In case the combustion values found at the beginning of the inter-
vention do not respect the standards in force or, in any case, do
not correspond to a proper combustion, contact the Technical
Assistant and have him carry out the necessary adjustments.
EN 676
Theoretical max.
GAS
CO
0 % O
G 20
11.7
G 25
11.5
G 30
14.0
G 31
13.7
34
GB
GAS OPERATION
Excess air
Max output
  1,2
Calibration
CO
%
2
2
 = 1,2
 = 1,3
2
9.7
9.0
9.5
8.8
11.6
10.7
11.4
10.5
Min output
  1,3
CO
mg/kWh
 100
 100
 100
 100

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rls 400/bp mx2003484420034845

Table of Contents