Bosch Condens 7000 FP Installation And Service Instructions Manual page 40

Floor standing gas condensing boiler
Table of Contents

Advertisement

Inspection and maintenance
1
2
3
Fig. 47 Undoing the supply air hose
[1]
Toggle clip
[2]
Supply air hose
[3]
Ventilation air collector
[4]
Temperature switch / burner controller connecting cable
▶ Loosen the gas pipe on the gas valve. For this purpose, remove the 4
screws on the flange (Fig. 48).
Fig. 48 Unscrew the screws on the air/gas ratio control valve
[1]
Screws on the flange (4x)
▶ Undo the temperature switch / burner controller connecting cable on
the mixture manifold (Fig. 47).
▶ Undo the connecting cable on the ignition transformer (Fig. 49,
[5]).
▶ Undo the electrical connections at the air/gas ratio control valve and
fan (Fig. 52, page 41).
▶ Remove the hoses on the differential pressure sensor (Fig. 52).
40
4
0010036138-001
1
4x
0010042379-001
▶ Remove the 4 fixing nuts (Fig. 49, [4]) at the top on the mixture
manifold.
1
2
3
4
5
Fig. 49 Undo the connecting cable and nuts on the ignition transformer
[1]
Ignition cable
[2]
Ignition cable
[3]
Monitor lead
[4]
Fixing nuts (4x)
[5]
Ignition transformer connecting cable
▶ Pull the mixture manifold with burner rod and fan back to the end
position (O-ring on the guide pin) (Fig. 50).
Fig. 50 Pull the burner back
[1]
Mixture manifold
▶ Install the insertion aid. When delivered, the insertion aid is attached
on the upper cover plate (Fig. 51).
Condens 7000 FP – 6721846699 (2022/12)
0010036144-001
1
0010036923-001

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gc7000fp 350Gc7000fp 400Gc7000fp 500

Table of Contents