Fig. 18 Transporting the floor standing boiler on rollers (measurements
in mm)
If the floor standing boiler is not to be brought into operation:
▶ Protect boiler from contamination.
Dispose of packaging in an environmentally responsible manner.
5

Installation

5.1

Installation location requirements

DANGER
Danger to life from explosion!
An increased and permanent ammonia concentration may lead to stress
corrosion cracking on brass (e.g.gas valves, union nuts). As a result,
there is a risk of explosion from gas escaping.
▶ Do not use wall mounted gas boilers in rooms where there is an
increased or permanent ammoniac concentration (e.g. livestock
stables or storage room for fertilisers).
▶ If contact with ammonia is unavoidable, make sure that there are no
brass parts installed in the system.
DANGER
Risk of fire through flammable materials or liquids.
▶ Never store flammable materials or liquids in the immediate vicinity
of the boiler.
Condens 7000 FP – 6721846699 (2022/12)
NOTICE
Risk of material damage due to contaminated combustion air!
▶ Do not use cleaning agents that contain chlorine or halogenated
hydrocarbons (e.g. in spray cans, solvents and cleaning agents,
paints and adhesives).
▶ Do not store or use these substances in the boiler room.
▶ Keep the combustion air supply free of dust or use the "air filter"
accessory set .
NOTICE
Material damage due to overheating!
Excessive ambient temperatures can result in heating system damage.
▶ Ensure the ambient temperature is above 0 °C and below 35 °C.
NOTICE
Frost damage!
▶ Install the heating system in a frost-free room.
5.2

Preventing noise disturbance for end-users

▶ Where the boiler surroundings are sensitive to noise (e.g. residential
units), use the silencer options offered by the manufacturer (flue gas
0010035212-001
silencer, expansion joints).
5.3

Single boiler (350...500)

When determining the installation location, take the clearances for the
flue gas routing and the connection pipe assembly into consideration (
Fig. 19).
Where applicable, allow extra wall clearances for additional
components, for example DHW cylinder, pipe connections or other
components on the flue gas side.
Fig. 19 Wall clearances at the installation location (right-hand version)
Installation
0010012544-001
17