Control Wire Sizes; Typical Electronic Thermostat Field Wiring - York ZWT06 Installation Manual

Table of Contents

Advertisement

5565606-TIM-B-1018
Thermostat Wiring
The thermostat should be located on an inside wall
approximately 56 inch above the floor where it will not be
subject to drafts, sun exposure or heat from electrical fixtures or
appliances. Follow the manufacturer's instructions enclosed
with thermostat for general installation procedure.Color-coded,
insulated wires should be used to connect the thermostat to the
THERMOSTAT
TERMINALS
W1
W2
1
Y1
Y2
G
R
3
C
RC
4
OCC
5
X
TERMINALS ON A
LIMITED NUMBER
OF THERMOSTATS
Second stage
1
Jumper is required if there is no Smoke Detector circuit.
2
Jumper is required for any co
3
OCC is an output from the thermostat to indicate the Occupied
4
X is an input to the thermostat to display Error Status condi ons.
5
Figure 24: Typical Electronic Thermostat Field Wiring
20
ot required on single stage he
g units.
of R, RC, or RH.
unit. Refer to Table 8 for control wire sizing and maximum
length.
Table 8: Control Wire Sizes
Wire Size
18 AWG
1. From the unit to the thermostat and back to the unit.
R~Occ Jumper:
CONTROL
TERMINAL
Smart Equipment Control boards come from the
BLOCK
factory with a jumper wire between R and OCC
terminals on the thermostat terminal strip. Failure
W1
to remove this jumper will place the unit into the
Occupied mode no matter what the occupancy
W2
demand is from the thermostat or EMS system.
Y1
To allow Thermostat or EMS control of the
Occupied mode for the unit, this jumper must be
G
removed during commissioning.
Y2
OCC
X
R
SD-24
C
C
24V
SD-24
Jumper Located on Harness
(If No Smoke Detector)
SD-R
R
on.
208/230-3-60 and 380/415-3-50 units control
transformers are factory wired for 230v and 415v power
supply respectively. Change tap on transformer for 208-
3-60 or 380-3-50 operation. See unit wiring diagram.
Maximum Length
150 Feet
Smoke
Detector
24 VAC
Class 2
2
(If Smoke Detector Is Used)
24V Output
Johnson Controls Ducted Systems
1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zw seriesZwt07Zwt08Zwt10Zwt12

Table of Contents