Mounting the control

0 mm
Fig. 9: Minimum distances for the circulation of ambient air
Additionally, provide sufficient distance for mounting, dismounting, plugs and cables.
10.3
Mounting the control
NOTICE
NOTICE
NOTICE
Bosch Rexroth AG
35 mm
35 mm
Damage of the device by plug mounting under voltage!
Before mounting or dismounting components, disconnect the control -
including its components - from voltage.
Connect the voltage only after the control and its components have been
set up.
Possible damage to property due to unintended mounting of the support rail
Fasten the support rail adequately.
Connect the support rail to a functional ground.
Mount the control on the support rail, as the support rail is also used for
heat dissipation and grounding.
Install the control in a control cabinet or an appropriate housing.
Control not fixed due to clamped support arm mounting!
Before mounting, ensure that the support arm mounting of the control is not
in open position. If required, release the clamping of the open position using
the locking lever, see
Figure
10.
ctrlX CORE