5.11
Gas feeding
Explosion danger due to fuel leaks in the pres-
ence of a flammable source.
Precautions: avoid knocking, attrition, sparks and
heat.
Make sure that the fuel interception tap is closed
before performing any operation on the burner.
5.11.1 Gas feeding line (Example) - Please refer to the gas train documentation for more information
Key (Fig. 18)
1
Manually operated shut-off valve
2
Pressure gauge
3
Filter
4
Governor
5a
Low pressure protection device
5b
Maximum gas pressure switch
6
1st safety shut-off device
7
2nd safety shut-off device
8
Ignition device
15
Valve leak detection control system
L
Gas train (supplied separately)
L1
Responsibility of the installer
L2
Burner
M1
Pressure test point
M2
Pressure test point
M3
Pressure test point
For applications according to the Pressure Equip-
ment Directive PED 2014/68/EU, the installer is
required to provide:
–
suitable means for draining and venting as de-
WARNING
fined in clause K.10 of DIN EN 676;
–
valve proving system as defined in clause K.
14.4 of DIN EN 676.
Installation
The fuel supply line must be installed by qualified
personnel, in compliance with current standards
and laws.
WARNING
19
GB
S10196
Fig. 18
20160598