Check For Refrigerant Leaks; Refrigerant Charge; No Charge; Low Charge Cooling - Payne PH3Z Installation Instructions Manual

13 seer single-packaged heat pump system
Hide thumbs Also See for PH3Z:
Table of Contents

Advertisement

c. Inspect all field- and factory-wiring connections. Be
sure that connections are completed and tight.
d. Ensure wires do not touch refrigerant tubing or sharp
sheet metal edges.
e. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb.
4. Verity the following conditions:
a. Make sure that outdoor-fan blade is correctly positioned
in fan orifice. Top edge of blade should be 3.125 in.(79
mm) down from outdoor coil outlet grille (size
024-048, See Fig. 19) or hub should be 0.708-in. (18
mm)
away from motor end bell (size 060, See Fig. 19).
See Outdoor Fan Adjustment section.
b. Make sure that air filter is in place.
c. Make sure that condensate drain pan and trap are filled
with water to ensure proper drainage.
d. Make sure that all tools and miscellaneous loose parts
have been removed.
START-UP
Step 1 — Check for Refrigerant Leaks
Proceed as follows to locate and repair a refrigerant leak and to
charge the unit:
1. Locate leak and make sure that refrigerant system pressure
has been
relieved
and
reclaimed
from
both
high-
and
low-pressure ports.
2. Repair leak following accepted practices.
NOTE:
Install a filter drier whenever the system has been opened
for repair.
Step 2 — Start-Up Cooling and Make Adjust-
ments
Complete
the
required
procedures
given
in the
Pre-Start-Up
section before starting the unit. Do not jumper any safety devices
when operating the unit. Do not operate the unit in cooling mode
when
the outdoor
temperature
is below
40°F
(4.4°C)
(unless
accessory low-ambient
kit is installed). Do
not rapid cycle the
compressor,
Allow
5
min.
between
"on"
cycles
to
prevent
compressor damage.
CHECKING
COOLING
OPERATION
Start and check the unit for proper cooling control operation as
follows:
1. Place room thermostat SYSTEM
switch in OFF position.
Observe
that blower
motor
starts when
FAN
switch
is
placed in ON position and shuts down within 60 sec. (for
024-042)
or 90 seconds
(for 048
and 060) when
FAN
switch is placed in AUTO position.
. Place SYSTEM switch in COOL position and FAN switch
in AUTO
position. Set control below
room
temperature.
Observe
that compressor,
outdoor
fan, and
indoor blower
motors start and that reversing valve shifts. Observe that
cooling cycle shuts down when control setting is satisfied.
Reversing valve (RV) remains energized.
AND
HEATING
CONTROL
3. Place
system
switch
in
HEAT
position.
Observe
that
compressor, indoor fan and outdoor fan energize (Reversing
Valve
is deenergized
in heat
pump
heating
mode).
Set
control above room temperature. Observe that heating cycle
shuts down when control setting is satisfied.
4. When
using
an
automatic
changeover
room
thermostat,
place both SYSTEM and FAN switches in AUTO positions.
Observe
that
unit
operates
in
Cooling
mode
when
temperature control is set to call for Cooling (below room
temperature),
and
unit
operates
in Heating
mode
when
temperature control is set to call for Heating (above room
temperature).
Step 3 — Refrigerant Charge
Refrigerant Charge — Amount
of refrigerant charge is listed on
unit nameplate and in Table 1. Refer to Payne Refrigerant Service
Techniques Manual, Refrigerants section. Unit panels must be in
place when unit is operating during charging procedure. Unit must
operate a minimum of 15 minutes before checking charge.
NO CHARGE
Refer
to Payne
Refrigerant
Service
Techniques.
Use
standard
evacuating
techniques.
After
evacuating
system,
weigh
in the
specified amount of refrigerant (refer to Table 1).
LOW CHARGE COOLING
024-042 units:
1. Measure suction line pressure by attaching a gauge to the
service port.
. Measure
the
suction
line
temperature
by
attaching
a
temperature sensing device to it.
3. Insulate the temperature sensing device so that the outdoor
ambient doesn't affect the reading.
4. Locate the measured suction line pressure in the top row of
Table 5 and the measured outdoor ambient temperature in
the
left
column
of the
table.
Based
on
the
two
values,
determine the required suction line temperature.
5. If the measured suction line temperature is greater than the
tabulated temperature, add charge in the system.
048 and 060 units:
1. Measure discharge line pressure by attaching a gauge to the
service port.
. Measure
the
liquid
line
temperature
by
attaching
a
temperature sensing device to it.
3. Insulate the temperature sensing device so that the outdoor
ambient doesn't affect the reading.
4. Refer to the required subcooling in Tables 3 to find the
required
subcooling
based
on
the
model
size
and
the
outdoor ambient temperature.
5. Interpolate if the outdoor temperature lies in between the
table values. Extrapolate if the temperature lies beyond the
table range.
6. Find
the pressure
value
corresponding
to the measured
pressure on the compressor discharge line.
7. Read across from the pressure reading to obtain the Liquid
line temperature for a required subcooling.
8. Add charge if the measured temperature is higher than the
liquid line temperature value in the table.
9, Add charge using the service connection on the suction line
of the compressor.
HEATING MODE CHARGE
Do not attempt to adjust charge by cooling methods while in heat
pump heating mode. Recover refrigerant and weigh in according to
unit data plate refrigerant data.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ph3z024Ph3z030Ph3z036Ph3z042Ph3z048Ph3z060

Table of Contents