Start-Up; Locate And Repair Refrigerant Leaks And; Start=L P Cooling Section And Make Adjustments; Checking - Payne PH1Z024 Installation Instructions Manual

Packaged heat pump units
Table of Contents

Advertisement

COMPRESSOR
TRANSFORMER
CONTACTOR
O
O
O
o
O
O
ELECTRIC
GROUND
INDOOR
OUTDOOR
FAN
MOTOR
HIGH
HEATER
LUG
FAN
AND
COMPRESSOR
VOLTAGE
FUSES
RELAY
START
CAPACITOR
LEADS
C00011
Fig.
12--Control
Box
Wiring
d. Inspect
coil fins. If damaged
during
shipping
and handling,
carefully
straighten
fins with a fin comb.
3. Verify
the %llowing
conditions:
a Make
sm'e that outdoor-tM_
blade
is CO,Teeth positioned
in fhn orifice
Top edge of blade should
be 3125
in down
t'rom outdoor
coil
outlet grille (size 024
048, See Fig. 21) or hub should be 0.70%in.
away fi'om motor end bell (size 060, See Fig. 22). See Outdoor
Fan
Adjustment
section.
b. Make
sure that air filter is in place.
c. Make
sure that condensate
&ain trap is filled with water
to ensure
proper
drainage.
d. Make
sure that all tools
and miscellaneous
loose parts
have been removed.
START-UP
Use the Start=L p Checklist supplied at the end of this book and proceed as follows:
PROCEDURE
I--CHECK
FOR REFRIGERANT
LEAKS
A.
LOCATE AND REPAIR REFRIGERANT
LEAKS AND CHARGE THE UNIT AS FOLLOWS:
1, Lsing both high- and tow-pressm'e ports, locate leaks and reclaim remaining refi'igerant to relieve system pressure,
2, Repair 1oak %ltowing accepted practices,
NOTE:
Install a liquid=line filter &ie* whenever the system has been opened for repair
PROCEDURE
2--START-UP
COOLING SECTION AND MAKE ADJUSTMENTS
Z_X
CAUTION:
Complete
the required
procedures
given
in the PreoStart-
Up section
this
page
before
starting
the unit,
Do
not jumper
any safety
devices
when
operating
the unit.
Do not operate
the compressor
when
the outdoor
temperature
is below
40 F,
Do not rapid-cycle
the compressor.
Allow
5 minutes
between
"on"
cycles
to prevent
compressor
damage.
A.
CHECKING
COOLING
CONTROL
OPERATION
Start and check the unit %r proper
cooling
control
operation
as %llows:
1. Place room thermostat
SYSTEM
switch
in OFF position
Obsmwe that blower
motor
starts when FAN" switch
is placed
in ON position
and
shuts down
within
30 seeconds
when
FAN switch
is placed
in AUTO
position
2. Place SYSTEM
switch
in COOL
position
and FAN switch
in AUTO
position.
Set cooling
control
below room temperature
Observe
that
compressor,
outdoor
tim,and indoor blower
motors
start and that reversing
valve shifts. Observe
that cooling
cycle shuts down when contloi
setting is satisfied.
Reversing
valve (RV)
remains
energized.
3. Place system
switch
in HEAT position.
Observe
that compressor,
indoor
tMa and outdoor
fire energize
(Reversing
Valve is deenergized
in
heat pump
heating
mode).
Set control
above room
temperature.
Observe
that heating
cycle shuts down
when control
setting
is satisfied.
12