Checking The Insulation Resistance - Siemens SIMOTICS T-1FW6 Operating Instructions Manual

Built-in torque motors
Hide thumbs Also See for SIMOTICS T-1FW6:
Table of Contents

Advertisement

Commissioning
7.3 Checking the insulation resistance
Are the motor power cables correctly connected to the power module with the UVW
phase sequence (clockwise rotating field)?
Do the temperature monitoring circuits fulfill the specifications of protective separation?
Important additional information on the temperature monitoring circuits Temp-S and
Temp-F are provided in the Configuration Manual "SIMOTICS T-1FW6 built-in torque mo‐
tors".
Before commissioning and switching on the DC link voltage for the first time, have you
checked the temperature monitoring circuits to ensure that they correctly trip?
Has the encoder been correctly connected?
Have the digital and analog signals been routed using separate cables?
When designing and installing, have you carefully complied with the EMC installation
directives of the inverter manufacturer?
Have the line-side and motor-side power cables been dimensioned and routed in accord‐
ance with the environmental and routing conditions?
Have the maximum permissible cable lengths between the frequency converter and the
motor (depending on the type of cables used) been observed?
7.3

Checking the insulation resistance

Notes for checking the insulation resistance
Installation inspection, preventive maintenance and troubleshooting are examples of required
checking of the insulation resistance on a machine/system with direct drives or directly on the
motors.
Risk of electric shock
If you check the insulation resistance using high voltage, this can damage the motor insulation.
There is a risk of death or serious injury if energized parts are touched.
• Only use test equipment that is in compliance with DIN EN 61557-1, DIN EN 61557-2 and
• Check the insulation resistance on the individual motors only according to the following
• If a DC voltage > 1000 V or an AC voltage is necessary to test the machine/system, then
• Carefully observe the operating instructions of the test device.
116
WARNING
DIN EN 61010-1 or the corresponding IEC standards.
procedure.
coordinate this test with your local sales partner.
Check
Operating Instructions, 09/2022, A5E52220812B AA
OK
 
 
 
 
 
 
 
 
1FW6 built-in torque motors

Advertisement

Table of Contents
loading

Table of Contents