Technician Settings P60 to P64

P60
Fan turns ON when the Cool or Heat valve reaches the
"Proportional ON percent"
P61
Fan turns OFF when the Cool or Heat valve drops
below the "Proportional OFF percent"
P60 – Proportional ON percent (FC only)
Range: 0...30%
Default: 30%
P61 – Proportional OFF percent (FC only)
Range: 0...100%
Default: 100%
P63 – Time on-delay between cooling stages (AC only)
Range: 0...600 seconds
Default: 5 seconds
P64 – Time off-delay between cooling stages (AC only)
Range: 0...600 seconds
Default: 1 seconds
ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential
Installation and Operation Guide
46
CARRIER CORPORATION ©2024
All rights reserved