Technician Settings P43 to P44

P43 – P44
Soft start in heat
with fan on demand (auto fan) active.
P43 – Soft start in heat – cut-in temperature (FC only)
The fan will not start before the temperature on T3 sensor reaches the
cut-in temperature.
See Technician Settings P08/P09.
Range: 14...37°C / 57...99°F
Default: 36°C / 97°F
P44 – Soft start in heat – cut-out temperature (FC only)
The fan will stop if the temperature on T3 sensor drops below the cut-out
temperature.
See Technician Settings P08/P09.
Range: 12...35°C / 54...95°F
Default: 32°C / 90°F