Motor noise, EMI measures

4.20 Motor noise, EMI measures

4.20.1 PWM carrier frequency and Soft-PWM control (Pr. 72, Pr. 240, Pr. 260)

You can change the motor sound.
Parameter
Number
72
PWM frequency selection
*1
240
Soft-PWM operation selection
*1
PWM frequency automatic
260
*2
switchover
*1
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in
Pr. 77 Parameter write selection.
*2
Reading and writing are enabled when "0 (SLD) or 1 (LD)" is set in Pr. 570.
(1) PWM carrier frequency changing (Pr. 72)
 You can change the PWM carrier frequency of the inverter.
 Changing the PWM carrier frequency produces an effect on avoiding the resonance frequency of a mechanical
system or motor or on EMI measures or on leakage current reduction caused by the PWM switching.
 Carrier frequencies under Real sensorless vector control or vector control are as shown below.
200V class (400V class)
FR-A720-02150 (FR-
A740-01100) or less
0 to 5
6 to 9
10 to 13
14, 15
 When using an option sine wave filter (MT-BSL/BSC) for the FR-A720-02880 (FR-A740-01440) or more, set "25"
(2.5kHz) in Pr. 72.
REMARKS
When "25" (available with the FR-A720-02880 (FR-A740-01440) or more) is set in Pr. 72, V/F control is forcibly selected.
288
Initial
Name
Value
2
1
1
Pr. 72 Setting
FR-A720-02880 (FR-
A740-01440) or more
0 to 5
6
Setting Range
200V class (400V class)
02150(01100)
0 to 15
or less
02880(01440)
0 to 6, 25
or more
0
1
0
1
Carrier Frequencies (kHz)
2
6
10
14
Description
PWM carrier frequency can be changed.
The setting displayed is in [kHz]. Note
that 0 indicates 0.7kHz, 15 indicates
14.5kHz and 25 indicates 2.5kHz.
Soft-PWM is invalid
"
When Pr. 72 = "0 to 5" (
0 to 4
A720-02880 (FR-A740-01440) or
more), soft-PWM is valid.
PWM carrier frequency is constant
independently of load.
When the carrier frequency is set to
3kHz or more (Pr. 72  "3"), perform
continuous operation at less than 85% of
the rated inverter current.
If the continuous operation is performed
with 85% of the rated current or higher
while the LD is set, the carrier frequency
is lowered to as low as 2kHz.
"
for FR-