Building management system gateway card (lonworks)
Hide thumbs Also See for CLIMATE 5000 VRF BMS-LON:

Advertisement

4 | INSTRUCTION

2.2.
EXTERNAL VIEW
15
22
251
NOTE
There is one installation methods as the following figure.
6 720 862 467 (2017/05)
168,8
291
319
3.
INSTRUCTION
3.1.
INFORMATION COLLECTION
This equipment provides information collected from the air
conditioning systems and reports through a BMS system.
61
3.2.
OPERATION CONTROL
The Unit provides BMS control of the air conditioning equipment.
You can change the operation mode, fan speed and the temperature
setting through the BMS.
CAUTION
1. Setting range of some air conditioner parameters are smaller than
the LNS's. Please refer to the operation manual to set the expected
value;
2. When use LNS to operate the air conditioner, it is suggested that
set mode, fan speed, and temperature to be the expected one
at a time.
3. Do not frequently use upper computer system as LNS etc. to send
or control orders to the air conditioner devices, for avoiding that
the operation state of the units may differ from the operation
expectation. Suggest that the operation interval time should be
over 10s, to make sure the timeliness and effectiveness of the
state changing of the air conditioners.
4. If suspension installed, make sure put the power supply termnal at
the upper side.
3.3.
CONNECTION ILLUSTATION
Connection Method 1
BMS-LON
LONWORKS
NET WORK
BMS
(suitable for all of the air conditioner systems)
Indoor units: Maximum of 64 units
RS485 (X Y E)
CLIMATE 5000 VRF