Building management system gateway card (lonworks)
Hide thumbs Also See for CLIMATE 5000 VRF BMS-LON:

Advertisement

Input network variables (n: 1~32; air conditioner address: 32~63)
NO.
Meaning
Operation mode
nviSetWork
1
setting
2
Fan speed setting
Temperature
3
nviSetTemp[n]
setting
* First power on, if there are no prior settings to the mode and fan speed, but set temperature, then this device will be operated as cool mode, and low
fan speed;
* First power on, if there are no prior settings to the mode and temperature, but set the fan speed, then this device will be operated as the cool mode,
and 24 degree;
* If there are no prior settings to the temperature and fan speed, but set the cool mode, then all the air conditioners will be operated as the cool mode,
24 degree, and low fan speed;
* If there are no prior settings to the temperature and fan speed, but set the heat mode, then all the air conditioners will be operated as the heat
mode, 24 degree, and low fan speed (Note: When set to heat mode the indoor unit will pre-heat first before the fan on the indoor unit will start.);
* Each time you only can set one of the mode settings, fan speed setting and temperature setting; combined settings must be finished individually.
CLIMATE 5000 VRF
Name
Type
SNVT_hvac_mode
Mode[n]
nviSetFan
SNVT_switch
Speed[n]
SNVT_temp_p
Definition
HVAC_AUTO 0
Initial value
HVAC_HEAT =1
Heat Mode
HVAC_COOL=3
Cool Mode
HVAC_FAN ONLY=9
Fan only Mode
HVAC_OFF=6
OFF Mode
* Beside the above value setting,the air conditioner
will respond as the cool mode, low fan and 24℃
LonMarker
Decimal system
10.0 1
LOW
14 01
20.0 1
MED
28 01
40.0 1
HIGH
50 01
100.0 1
AUTO
C8 01
* Do not suggest setting other value except the
above value setting.
LonMarker
Decimal system
17.00=17℃
18.00=18℃
19.00=19℃
20.00=20℃
21.00=21℃
22.00=22℃
23.00=23℃
24.00=24℃
25.00=25℃
26.00=26℃
27.00=27℃
28.00=28℃
29.00=29℃
30.00=30℃
For air conditioner: less than 17, then will be
treated as 17; larger than 30, then will be treated
as 30; non-integer setting between 17~30, only
treat its integer part, such as 24.5, it will be
treated as 24
For upper side unit systems: be rounded to 2
decimal places
NETWORK VARIABLE CHARTS | 11
Specifications
Set operation mode
NLUtil Node Utility
Hexadecimal system
LOW
MED
Set fan speed
HIGH
AUTO
NLUtil Node Utility
Hexadecimal system
06 A4
07 08
07 6C
07 D0
08 34
08 98
08 FC
09 60
09 C4
0A 28
Set temperature
0A 8C
Initial value=24℃
0A F0
0B 54
0B B8
6 720 862 467 (2017/05)