Cleaning Heat Exchangers - Carrier 59SC2A Installation, Start-Up, Operating And Service And Maintenance Instructions

Single stage 4—way multipoise condensing gas furnace
Hide thumbs Also See for 59SC2A:
Table of Contents

Advertisement

9, Turn gas on at electric switch on gas valve and at external
shut-off or meter
10. Turn power on at external disconnect, fuse or circuit break-
er.
11. Run the furnace through two complete heating cycles to
check for proper operation
12. Install control door when complete.
Checking Heat Pad Operation (If Applicable)
In applications where the ambient temperature around the furnace
is 32°F or lower, freeze protection measures are required. If this
application is where heat tape has been applied, check to ensure it
will operate when low temperatures are present.
NOTE:
The Heat Pad, when used, should be wrapped around the
condensate drain trap. There is no need to use heat tape within the
furnace casing. Most heat tapes are temperature activated, and it is
not practical to verify the actual heating of the tape. Check the
following:
1. Check for signs of physical damage to heat tape such as
nicks, cuts, abrasions, gnawing by animals, etc.
2. Check for discolored heat tape insulation. If any damage or
discolored insulation is evident, replace heat tape.
3. Check that heat tape power supply circuit is on.
Cleaning Heat Exchangers
The
following
items must be performed
by a qualified service
technician.
Primary Heat Exchangers
If the heat exchangers get an accumulation of light dirt or dust on
the inside, they may be cleaned by the following procedure:
NOTE:
If the heat exchangers get a heavy accumulation of soot
and
carbon,
both
the primary
and
secondary
heat exchangers
should be replaced rather than trying to clean them thoroughly due
to their intricate design. A build-up of soot and carbon indicates
that a problem exists which needs to be corrected, such as improper
adjustment
of manifold
pressure,
insufficient
or
poor
quality
combustion
air,
improper
vent
termination,
incorrect
size
or
damaged
manifold
orifice(s), improper
gas, or a restricted heat
exchanger (primary or secondary). Action must be taken to correct
the problem.
1. Turn off gas and electrical supplies to furnace.
A A
SS
ELECTRICAL
SHOCK,
FIRE
OR
EXPLOSION
HAZARD
Failure
to follow
this warning
could
result
in personal
injury or death, or property damage.
Before
installing,
modifying,
or servicing
system,
main
electrical disconnect switch must be in the OFF position and
install
a lockout
tag.
There
may
be
more
than
one
disconnect switch.
Lock out and tag switch with a suitable
warning label. Verify proper operation after servicing.
A A
SS
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
Turn off the gas and electrical supplies to the furnace and
install lockout tag before performing
any
maintenance
or
service.
Follow
the
operating
instructions
on
the
label
attached to the furnace.
. Remove control door.
. Disconnect wires or connectors to flame rollout switch, gas
valve, igniter, and flame sensor.
4. Using backup wrench, disconnect gas supply pipe from fur-
nace gas control valve.
5. Remove two screws attaching top filler plate and rotate up-
wards to gain access to screws attaching burner assembly to
cell panel.
6. Remove
screws
attaching burner assembly
to cell panel.
See Fig. 63.
NOTE:
Burner cover, manifold, gas valve, and burner assembly
should be removed as one assembly.
7, Clean heat exchanger openings with a vacuum and a
soft
brush.
See Fig. 60.
NOTE:
After cleaning, inspect the heat exchangers to ensure they
are free of all foreign objects that may restrict flow of combustion
products.
8. Reverse items 6 through 1 for reassembly.
9, Refer to furnace wiring diagram
and reconnect wires to
flame rollout switch, gas valve, igniter, and flame sensor.
10. Turn on gas and electrical supplies to furnace.
11. Check furnace operation through 2 complete heat operating
cycles. Look at burners. Burner flames should be clear blue,
almost transparent.
See Fig. 61.
12. Check for gas leaks.
CA
AUN Le
FIRE OR EXPLOSION HAZARD
Failure
to follow
this warning
could
result
in personal
injury, death, and/or property damage.
Never purge a gas line into a combustion chamber. Never
test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection
of leaks to check all connections.
A fire or explosion may
result causing property damage, personal injury or loss of
life.
13. Replace main furnace door.
Secondary Heat Exchangers
The
condensing
side (inside) of the secondary
heat exchanger
CANNOT
be serviced or inspected without complete removal of
the
heat
exchanger
assembly.
Detailed
information
on
heat
exchanger removal can be obtained from your Distributor.
WINTERIZATION
4&
CAUTION
UNIT AND PROPERTY DAMAGE
HAZARD
Failure to follow this caution may result in unit component or
property damage.
If the furnace is installed in an unconditioned space where the
ambient temperatures may be 32° F (0° C) or lower, freeze
protection measures must be taken to prevent minor property
or product damage.
Since the furnace uses a condensing heat exchanger, some water
will accumulate in the unit as a result of the heat transfer process.
Therefore,
once it has been operated, it cannot be turned off and
left off for an extended period of time when
temperatures will

Advertisement

Table of Contents