Replace The Reversing Valve - Friedrich VERT-I-PAK VHA09K25RTQ Service Manual

Single package vertical heat pump system r-410a refrigerant
Table of Contents

Advertisement

R-410A SEALED SYSTEM REPAIRS

Replace The Reversing Valve

HIGH PRESSURE HAZARD
Sealed Refrigeration System contains refrigerant
and oil under high pressure.
Proper safety procedures must be followed,
and proper protective clothing must be worn
when working with refrigerants.
Failure to follow these procedures could
result in serious injury or death.
1. Install Process Tubes. Recover refrigerant from sealed system. PROPER HANDLING OF RECOVERED REFRIGERANT
ACCORDING TO EPA REGULATIONS IS REQUIRED.
2. Remove solenoid coil from reversing valve. If coil is to be reused, remove solenoid and protect from heat while changing
valve.
3. Unbraze all lines from reversing valve.
4. Clean all excess braze from all tubing so that they will slip into fittings on new valve.
5. Remove solenoid coil from new valve.
6.
Protect new valve body from heat while brazing with plastic heat sink (Thermo Trap) or wrap valve body with wet rag.
7. Fit all lines into new valve and braze lines into new valve.
8. Pressurize sealed system with trace amounts of R-410A and nitrogen up to 550 psi. Perform Triple evacuation , Refer
to Sealed
system method of charging..
standards.
9. Once the sealed system is leak free, install solenoid coil on new valve and charge the sealed system by weighing in the
proper amount and type of refrigerant as shown on rating plate. Crimp the process tubes and solder the ends shut. Do not leave
Schrader or piercing valves in the sealed system.
NOTE: When brazing a reversing valve into the system, it is of extreme importance that the temperature of the valve does not
exceed 250°F at any time.
Wrap the reversing valve with a large rag saturated with water. "Re-wet" the rag and thoroughly cool the valve after each
brazing operation of the four joints involved.
The wet rag around the reversing valve will eliminate conduction of heat to the valve body when brazing the line connection.
56
WARNING
EXPLOSION HAZARD
The use of nitrogen requires a pressure
regulator. Follow all safety procedures and
wear protective safety clothing etc.
Failure to follow proper safety procedures
could result in serious injury or death.
Leak check the system, using a suitable leak detector according to HVAC industry
The use of a torch requires extreme care and proper
judgment. Follow all safety recommended precautions and
notice could result in moderate to serious property damage.
WARNING
NOTICE
FIRE HAZARD