Correct CFM (if needed): Correction Multipliers
230V
208V
265V
Heating
Cooling

Explanation of Tables

Table 401 is the nominal dry coil VERT-I-PAK CFMs. Table 402 is the correction factors beyond nominal conditions.
1 ½ TON SYSTEM ( 18,000 Btu)
Operating on high speed @ 230 volts with dry coil.
measured external static pressure .10
Air Flow = 450 CFM
In the same SYSTEM used in the previous example but having a WET coil you must use a correction factor of .95 (i.e. 450 x .95=428 CFM) to
allow for the resistance (internal) of the condensate on the coil.
It is important to use the proper procedure to check external Static Pressure and determine actual airflow. Since in the case of the VERT-I-
PAK, the condensate will cause a reduction in measured External Static Pressure for the given airflow.
It is also important to remember that when dealing with VERT-l-PAK units that the measured External Static Pressure increases as the
resistance is added externally to the cabinet. Example: duct work, filters, grilles.

Indoor Airflow Data

The Vert-I-Pak A series units must be installed with a free return air configuration. Table 401 lists the indoor airflow at corresponding static
pressures. All units are rated at low speed.

Ductwork Preparation

If flex duct is used, be sure all the slack is pulled out of the flex duct. Flex duct ESP can increase considerably when not fully extended. DO
NOT EXCEED a total of .30 ESP, as this is the MAXIMUM design limit for the VERT-I-PAK A-Series unit.
IMPORTANT: FLEX DUCT CAN COLLAPSE AND CAUSE AIRFLOW RESTRICTIONS. DO NOT USE FLEX DUCT FOR: 90 DEGREE BENDS, OR
UNSUPPORTED RUNS OF 5 FT. OR MORE.
29
External Static Pressure
Table 402 (Correction Multiplier)
1.00
0.97
1.00
0.95