Outdoor Fan Check - Friedrich VERT-I-PAK VHA09K25RTQ Service Manual

Single package vertical heat pump system r-410a refrigerant
Table of Contents

Advertisement

COMPONENT TESTING

Outdoor Fan Check

1. Remove Electrical box cover.
2. Ensure that unit is running with a demand for outdoor fan.
3. Check for 230 VAC by placing multi meter probes on Contactor
Terminal and fan Out terminal of the defrost control board.
4. If 230 VAC is present- remove power from unit and check for
loose terminals.
5. Replace motor.
Place Red lead here
Place Black lead here