Carrier RHV090-120 Installation Instructions Manual page 34

Single package rooftop heat pump with r-410a refrigerant and x-vane fan technology
Table of Contents

Advertisement

MENU
PARAMETER
ERV OAT SP
EXH1 SET
EXH1 L SET
EXH1 M SET
SETPOINTS
(cont)
EXH1 H SET
EXH2 L SET
EXH2 M SET
EXH2 H SET
INSTALL
UNITS DEG
EQUIPMENT
AUX2 IN
FAN SPEED
SYSTEM
SETUP
FAN CFM
AUX1 OUT
OCC
FACTORY DEFAULT
MA LO SET
ADVANCED
FREEZE POS
SETUP
CO2 ZERO
CO2 SPAN
34
Table 10 — W7220 Menu Structure
PARAMETER
DEFAULT
VALUE
0°F to 50°F
f
32°F
(–18°C to 10°C);
increment by 1°F
50%
0 to 100%
65%
0 to 100%
60%
0 to 100%
50%
0 to 100%
80%
0 to 100%
77%
0 to 100%
75%
0 to 100%
01/01/17
N/A
F
F or C
Conventional or
CONV
HP
SD/W or
W
HP(O)/HP(B)
1 speed
2 speed
2 speed
2SP H/C
3 speed
100 to 15000 cfm;
5000cfm
increment by 100
NONE
ERV
NONE
EXH2
SYS
INPUT or
INPUT
ALWAYS
NO
NO or YES
35°F to 55°F
(2°C to 13°C);
45°F
Incremented by
10°F
CLO
CLO or MIN
0 to 500 ppm;
0ppm
Increment by 10
1000 to 3000 ppm;
2000ppm
Increment by 10
Specifications subject to change without notice.
a
PARAMETER
RANGE AND
INCREMENT
b
ENERGY RECOVERY VENTILATOR UNIT OUTDOOR AIR
TEMPERATURE SETPOINT
Only displayed when AUX1 O = ERV
Exhaust fan set point for single speed units. Based on OA Damper
position to activate power exhaust.
EXHAUST FAN 1 SETPOINT AT LOW SPEED on 2 speed or 3
speed with 1 heat and 2 cool. Based on economizer OA damper
position to activate power exhaust.
EXHAUST POINT 1 SETPOINT AT MEDIUM SPEED. Only
displays if unit is set for 3 speed with 1 heat and 2 cool. Based on
economizer OA damper position to activate power exhaust.
EXHAUST FAN 1 SETPOINT AT HIGH SPEED on 2 speed or 3
speed with 1 heat and 2 cool. Based on economizer OA damper
position to activate power exhaust.
EXHAUST FAN 2 SETPOINT AT LOW SPEED on 2 speed or 3
speed with 1 heat and 2 cool. Based on economizer OA damper
position to activate power exhaust.
EXHAUST FAN 2 SETPOINT AT MEDIUM SPEED. Only displays
if unit is set for 3 speed with 1 heat and 2 cool. Based on
economizer OA damper position to activate power exhaust.
EXHAUST FAN 2 SETPOINT AT HIGH SPEED on 2 speed or 3
speed with 1 heat and 2 cool. Based on economizer OA damper
position to activate power exhaust.
Display order = MM/DD/YY
Setting order = DD, MM, then YY.
Sets economizer controller in degrees Fahrenheit or Celsius.
CONV = conventional;
HP O/B = Enable Heat Pump mode. Use AUX2 I for Heat Pump
input from thermostat or controller.
In CONV mode:
SD + Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode.
NOTE: If using 2-speed fan mode, you must program CONV mode
for W. Shutdown is not available in 2-speed fan mode.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on heat.
Sets the economizer controller operation based on 1 speed, 2
speed, 2 speed heat/cool (2SP H/C), or 3 speed supply fan.
NOTE: Multi-speed fan options also need Heat (W1) programmed
in AUX 2 IN.
g
UNIT DESIGN AIRFLOW (CFM)
Enter only if using DCVAL ENA = AUTO
The value is found on the nameplate label for the specific unit.
Select OUTPUT for AUX1 O relay
• NONE = not configured (output is not used)
• ERV = Energy Recovery Ventilator
• EXH2 = second damper position relay closure for second exhaust
fan
• SYS = use output as an alarm signal
OCCUPIED MODE BY EXTERNAL SIGNAL
When using a setback thermostat with occupancy out (24 vac), the
24 vac is input "INPUT" to the OCC terminal. If no occupancy
output from the thermostat then change program to "ALWAYS" OR
add a jumper from terminal R to OCC terminal.
Resets all set points to factory defaults when set to YES. LCD will
briefly flash YES and change to NO but all parameters will change
to the factory default values.
NOTE: RECHECK AUX2 IN and FANTYPE for required 2-speed
values.
SUPPLY AIR TEMPERATURE LOW LIMIT
Temperature to achieve Freeze Protection (close damper and
alarm if temperature falls below setup value).
FREEZE PROTECTION DAMPER POSITION
Damper position when freeze protection is active (closed or MIN
POS).
CO
ppm level to match CO
2
CO
ppm span to match CO
2
(cont)
NOTES
g
f
sensor start level.
2
sensor.
2
RHV-090-120-01SI
g