Omron F3S-B122P-L Instruction Manual page 5

Safety light curtain
Table of Contents

Advertisement

F3S-B
The F3S-B is a TYPE 2 Electro-sensitive protective equipment, intended to be used as or with the safety
related part of control system to category 2,1, or B as defined in the European standard EN954-1.
Do not use the F3S-B in category 3 or 4 systems.
Do not use the F3S-B on machines that cannot be stopped by electrical control in case of an emergency.
Install protective structures around the machine so that you must pass through the detection zone to
reach a hazardous part of the machine (see "2-1 Installation Conditions").
Install the F3S-B so that some part of the operator's body remains in the detection zone at all times
when the operator works in a hazardous area (see "2-1 Installation Conditions").
Failure to do so may result in serious injury.
A qualified person, as determined by local regulations, must confirm that installation, inspection and
maintenance are implemented correctly.
Always maintain the safety distance between the F3S-B and a hazardous part of a machines (see "2-1
Installation Conditions").
Do not install the F3S-B in a location affected by wall reflections (see "2-1 Installation Conditions").
Do not short the output lines to the +24 V line. Doing so will cause the output to be always ON, creating
a hazardous situation.
Do not connect the F3S-B to a power supply with voltage higher than 24 VDC + 20 %.
Do not connect the F3S-B to an AC power supply.
Be sure to conduct inspections regularly (see "6 Maintenance").
The F3S-B cannot be used in applications where hazardous projectiles may exit the protected zone.
Do not disassemble, repair or modify the F3S-B.
Do not use the F3S-B in flammable or explosive environments.
DC power supply units must satisfy all of the conditions below so that the F3S-B can comply with the
applicable standards IEC 61496-1 and UL 508.
The power supply voltage must be within rating (24 VDC ± 20 %).
The power supply is connected only to the F3S-B and to the devices related to the electro-sensitive
protective function of the F3S-B, such as a safety controller and muting sensors, and it has enough
rated current for all the devices. The power supply is not connected to other devices or machines.
The power supply uses double or reinforced insulation between the primary and secondary circuits
The power supply has automatic reset characteristics (voltage drop) to protect overcurrent.
The power supply maintains an output holding time of at least 20 ms.
FG (frame ground terminal) must be connected to PE (protective earth) when using a commercially
available switching regulator.
The power supply must have output characteristics required for the power source for Class 2 Circuit
or Limited Voltage/Current Circuit as defined in UL508 (see "2-3-1 Remark").
The power supply must conform to regulatory requirements and standards, regarding EMC and elec-
trical equipment safety, of the country where the F3S-B is installed and where machinery will be op-
erated, for example: The EMC Directive (industrial environment) and the Low Voltage Directive in
EU.
Do not use the F3S-B in a retroreflective configuration. Otherwise detection may fail.
4