Diagnostics and troubleshooting

8.2 Diagnostics/Remote function test

8.2
Diagnostics/Remote function test
The units starts a self diagnostics routine when the power supply is applied or interrupted for
>2 seconds.
The loop current shows following behavior, which can be evaluated by an external signal
conditioning instrument (accessory) or by a PLC:
60
Loop current / mA
Power supply applied
Diagnostics test is o.k. Measurement signal is present:
Loop current = 8 or 16mA
Relay = open or closed (depending on selected output logic, see Output logic (Page 30))
Diagnostics test is o.k. Measurement signal is present:
Loop current = 8 or 16mA
Relay = open or closed (depending on selected output logic, see Output logic (Page 30))
Diagnostics test failed:
Loop current <=3,6mA
Relay = open
sec
SITRANS LCS100 2-wire mA and Relay Version
Operating Instructions, 05/2023, A5E52142831-AA