Operating Instructions · April 2008
SITRANS LVL100

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SITRANS LVL100

  • Page 1 Operating Instructions · April 2008 SITRANS LVL100...
  • Page 2: Table Of Contents

    Dismounting steps ..... . 24 Disposal ......24 SITRANS LVL100 l CONTACTLESS ELECTRONIC SWITCH...
  • Page 3 Technical data......25 Dimensions ......28 SITRANS LVL100 l CONTACTLESS ELECTRONIC SWITCH...
  • Page 4: About This Document

    This symbol indicates special instructions for Ex applications. List The dot set in front indicates a list with no implied sequence. à Action This arrow indicates a single action. Sequence Numbers set in front indicate successive steps in a procedure. SITRANS LVL100 l CONTACTLESS ELECTRONIC SWITCH...
  • Page 5: For Your Safety

    During work on and with the device the required personal protection equipment must always be worn. 2.2 Appropriate use SITRANS LVL100 is a sensor for level detection. You can find detailed information on the application range in chapter "Product description".
  • Page 6: Safety Approval Markings And Safety Tips

    The safety approval markings and safety tips on the device must be observed. 2.6 CE conformity SITRANS LVL100 is in CE conformity with EMC (89/336/ EWG), fulfils NAMUR recommendation NE 21 and NE 23 and is in CE conformity with NSR (73/23/EG).
  • Page 7: Product Description

    SITRANS LVL100 point level sensor Test magnet Documentation - this operating instructions manual - if necessary, certificates SITRANS LVL100 consists of the following components: Components Housing with electronics process fitting with tuning fork Fig. 1: SITRANS LVL100 The type label contains the most important data for identi- Type label fication and use of the instrument:...
  • Page 8: Principle Of Operation

    Product description Technical data Article numbers, documentation 3.2 Principle of operation SITRANS LVL100 is a point level sensor with tuning fork for Area of application level detection. It is designed for industrial use in all areas of process technology and can be used in liquids.
  • Page 9: Operation

    Data for power supply are specified in chapter "Technical data". 3.3 Operation The switching status of SITRANS LVL100 can be checked with closed housing (signal lamp). Products with a density > 0.7 g/ cm³ (0.025 lbs/in³) can be detected. 3.4 Storage and transport Your instrument was protected by packaging during transport.
  • Page 10: Mounting

    The switching point refers to water (1 g/cm³/0.036 lbs/in³). When mounting SITRANS LVL100, make sure that this marking is at the height of the requested switching point. Keep in mind that the switching point of the instrument is shifted if the medium has a density other than water.
  • Page 11 This applies mainly to mounting outdoors, in areas where moisture is expected (e.g. by cleaning processes) or on cooled or heated vessels. Fig. 4: Measures against moisture penetration Do not hold SITRANS LVL100 on the tuning fork. Transport SITRANS LVL100 l CONTACTLESS ELECTRONIC SWITCH...
  • Page 12: Mounting Instructions

    SITRANS LVL100 is in the same position after being screwed in. Remove therefore the supplied flat seal from the thread of SITRANS LVL100. This flat seal is not required when using a welded socket with front-flush seal. Before welding, unscrew SITRANS LVL100 and remove the rubber ring from the welded socket.
  • Page 13 The position of the tuning fork is indicated by a marking on the hexagon of SITRANS LVL100. With this, you can check the position of the tuning fork when screwing it in. When the hexagon touches the seal, the thread can still be turned by approx.
  • Page 14 If SITRANS LVL100 is mounted in the filling stream, unwanted Inflowing medium false measurement signals can be generated. For this reason, mount SITRANS LVL100 at a position in the vessel where no disturbances, e.g. from filling openings, agitators, etc., can occur.
  • Page 15: Connecting To Power Supply

    Always keep in mind the following safety instructions: Note safety instructions Connect only in the complete absence of line voltage SITRANS LVL100 is connected with standard cable with round Selecting connection cable cross section. Select the outer diameter of the cable respectively so that the seal effect of the cable gland is...
  • Page 16 Plug housing Plug insert Profile seal Control lamp 10 SITRANS LVL100 We recommend connecting SITRANS LVL100 in such a way Contactless electronic switch that the switching circuit is open when there is a level signal, line break or failure (safe condition).
  • Page 17 Connecting to power supply Max. Min. Fig. 8: Wiring plan, contactless electronic switch with valve plug DIN 43650 PE Protective ground RL Load resistance (contactor, relay, etc.) SITRANS LVL100 l CONTACTLESS ELECTRONIC SWITCH...
  • Page 18: Set Up

    The switching status of the electronics can be checked on the upper part of the housing. 6.2 Function test SITRANS LVL100 has an integrated test switch which can be activated magnetically. Proceed as follows to test the instru- ment: à Hold the test magnet (accessory) to the magnet symbol on the instrument housing Fig.
  • Page 19: Functional Chart

    Level Switching status Control lamp Mode max. Switch closed Green Mode max. Switch open Mode min. Switch closed Green Mode min. Switch open Failure Switch open flashes red SITRANS LVL100 l CONTACTLESS ELECTRONIC SWITCH...
  • Page 20: Maintenance And Fault Rectification

    Shortcircuit or overload à Check the electrical connection Depending on the failure reason and measures taken, the Reaction after fault rec- tification steps described in chapter "Set up" must be carried out again, if necessary. SITRANS LVL100 l CONTACTLESS ELECTRONIC SWITCH...
  • Page 21: Exchange Electronics

    Take note of the specifications in the corresponding operating instructions. Proceed as follows to exchange the electronics module: 1 Separate SITRANS LVL100 from operating voltage 2 Loosen fixing screw (1) of the valve plug (2) with a wrench 3 Remove valve plug (2) according to drawing 4 Remove lateral fixing screw (7) with a crosstip screwdriver...
  • Page 22 Maintenance and fault rectification Fig. 14: Exchange electronics Fixing screw Valve plug DIN 43650 Profile seal Electronics module Rotary switch (16-steps) Connection plug Fixing screw Housing SITRANS LVL100 l CONTACTLESS ELECTRONIC SWITCH...
  • Page 23: Instrument Repair

    Maintenance and fault rectification 7.4 Instrument repair If it is necessary to repair the instrument, please contact Siemens Milltronics Process Instruments Inc. You find the locations on our homepage "www.siemens.com/processauto- mation". SITRANS LVL100 l CONTACTLESS ELECTRONIC SWITCH...
  • Page 24: Dismounting

    Correct disposal avoids negative effects to persons and environment and ensures recycling of useful raw materials. Materials: see chapter "Technical data" If you cannot dispose of the instrument properly, please contact us about disposal methods or return. SITRANS LVL100 l CONTACTLESS ELECTRONIC SWITCH...
  • Page 25 -40 … +70 °C (-40 … +158 °F) Storage and transport temperature -40 … +80 °C (-40 … +176 °F) Process conditions -1 … 64 bar/-100 … 6400 kPa (- Process pressure -14.5 … 928 psig) SITRANS LVL100 l CONTACTLESS ELECTRONIC SWITCH...
  • Page 26 (284 °F) (302 °F) Fig. 16: Dependendency ambient temperature to process temperature Ambient temperature in °C (°F) Process temperature in °C (°F) Temperature shock no limitation 0.1 … 10000 mPa s Viscosity - dynamic SITRANS LVL100 l CONTACTLESS ELECTRONIC SWITCH...
  • Page 27 4.5 … 7 mm (0.18 … 0.28 in) - Outer cable diameter Electrical protective measures Protection - Valve plug DIN 43650 IP 65 Overvoltage category Protection class Approvals Overfill protection according to WHG (available from July 2008) Ship approvals SITRANS LVL100 l CONTACTLESS ELECTRONIC SWITCH...
  • Page 28 ") ø31,7mm ") ø21,3mm ") Fig. 17: SITRANS LVL100 - standard version Switching point Length with G¾ A, ¾ NPT: 66 mm (2.6 in) Length with G1 A, 1 NPT: 69 mm (2.7 in) SITRANS LVL100 l CONTACTLESS ELECTRONIC SWITCH...
  • Page 29 "NPT G1A, 1"NPT ø21,3mm ") Fig. 18: SITRANS LVL100 - high temperature version Thread G¾ A, G1 A (DIN ISO 228/1), ¾ NPT or 1 NPT (valve plug DIN 43650) Tri-Clamp (valve plug DIN 43650) Switching point Length with G¾ A, ¾ NPT: 66 mm (2.6 in) Length with G1 A, 1 NPT: 69 mm (2.7 in)
  • Page 30 Supplement Fig. 19: SITRANS LVL100 - high temperature version Bolting (valve plug DIN 43650) SMS 1145 (valve plug DIN 43650) Switching point Length with bolting: 53 mm (2.1 in) Length with SMS 1145: 53 mm (2.1 in) SITRANS LVL100 l CONTACTLESS ELECTRONIC SWITCH...
  • Page 31 Supplement SITRANS LVL100 l CONTACTLESS ELECTRONIC SWITCH...
  • Page 32 © Siemens Milltronics Process Instruments Inc. 2008 Subject to change without prior notice *7ML19985KN01* Rev. 1.0 33843-EN-080421...