Diagnostics And Troubleshooting; Troubleshooting - Siemens SITRANS L LCS100 Operating Instructions Manual

Table of Contents

Advertisement

Diagnostics and troubleshooting

8.1

Troubleshooting

LEDs
Green
Yellow
Power
Signal
supply
output
OFF
OFF
ON
ON or OFF
ON
ON or OFF
ON
ON or OFF
ON
OFF
ON
Blinks
for a few
times,
then
stops
blinking
ON
OFF
ON
ON or OFF
ON
ON or OFF
59
Behaviour
White Probe
cov-
ered/uncovered
OFF
ON
Probe is uncovered but
LED white states cov-
ered
OFF
Probe is covered but LED
white states uncovered
ON or OFF
Yellow LED lights oppo-
site to white LED when
this is not meant to
happen
Blinks slowly (eve-
Relay = idle
ry 2 seconds)
ON or OFF
Blinking happens after
the potentiometer was
turned
Blinks fast (twice
Current loop = 3.6mA,
per second)
Relay = idle
ON or OFF
No respond (change of
white and yellow LED)
when potentiometer is
turned and probe is
uncovered
ON or OFF
Unequal current in cur-
rent loop
Cause
Proper power supply
not
applied to device
Connector came loose
Defective component in
device
Sensitivity is set too
high. Either sensitivity
setting not properly
done or too much ma-
terial buildup
Sensitivity is set too
low. Either sensitivity
setting not properly
done or too low dielec-
tric constant from ma-
terial.
Incorrect polarity on
power supply
Potentiometer is on the
clockwise stop position
and thus the 4-20mA
continuous mode is
active.
This is a normal
operation. The blinking
indicates the position of
the potentiometer after
it
was turned.
Diagnostics has indicat-
ed a failure
Defective component in
device
Loop circuitry is con-
nected against earth
SITRANS LCS100 2-wire mA and Relay Version
Operating Instructions, 05/2023, A5E52142831-AA
8
Action
Check power supply
Refasten connector
Contact distributor
Reduce sensitivity (see
Operating elements
(LEDs) (Page 39)). If
applicable clean probe
from buildup
Increase sensitivity (see
Operating elements
(LEDs) (Page 39)). Die-
lectric constant of mate-
rial must be 1.5 or more
Reverse polarity on
power supply. See Out-
put logic (Page 30).
If the switch mode is
required, go to
switchpoint setting (see
Operating elements
(LEDs) (Page 39))
No action required
Contact distributor
Contact distributor
Remove earth connec-
tion from loop circuitry