TROUBLESHOOTING THE ECM MOTOR
EcoBlue™ motors are designed with several built-in protections
included in the motor software. If the motor detects a fault it will
safely shut down. For temperature related faults the motor requires
a line voltage reset to continue operation. For all others, the motor
will resume operation automatically as soon as the fault condition
is cleared. See Table 2 for a complete list.
r
Table 2 — Fault Condition/Reset Trigger
FAULT
RESET
CONDITION
TRIGGER
Phase Failure
Automatic
Locked/
Automatic
Blocked Rotor
Motor
Manual
Overheated
Power Module
Manual
Overheated
Line under-
Automatic
voltage
Communication
Automatic
Error
Troubleshooting the motor requires a voltmeter.
1.
Disconnect main power to the unit.
2.
Disconnect motor plug in supply section of the unit.
3.
Restore main unit power.
4.
Check for proper line voltage at motor power leads Black
(PL1-1), Yellow (PL1-2), and Blue (PL1-3). Blue is only
present on 3-phase motors. See the following table.
50FCQ UNIT VOLTAGE MOTOR VOLTAGE
208/230
460
575
5.
Disconnect main power.
6.
Reconnect motor plug in supply section of unit.
7.
Restore main power.
8.
Check for proper motor control voltage signal of 9.7 vdc
to 10.3 vdc at IFM-1 and IFM-3 on Unit Control Board
(UCB). See Fig. 10.
9.
Using a jumper wire from unit control terminals R to G,
engage motor operation.
10. Verify control signal from user speed selection switch by
placing voltmeter taps in provided terminals marked vdc.
Signal should be between 3.8 vdc and 10.3 vdc.
11. If the motor does not start and run, remove the fan assem-
bly and replace the motor with one having the same part
number. Do not substitute with an alternate design motor
as the voltage/speed programming will not be the same as
that on an original factory motor.
DESCRIPTION
One phase is missing or imbalanced. In
this case the motor will come to a stop
and then automatically restart when all
phases are present.
The rotor is blocked. Once the locking
mechanism has been removed, the
motor will automatically restart.
The motor will stop in the event the
motor overheats. In this case there has
to be a manual restart.
The motor will stop in the event the
electronics overheat. In this case there
has to be a manual restart.
Once the line voltage returns within
permitted operating range, the fan will
automatically restart.
Internal communication error of the
fan's electronics. The fan will restart
automatically, if error is cleared.
MINIMUM-
MAXIUMUM VOLTS
230
190-250
230
210-250
460
420-500
Fig. 10 — Supply Fan Control Wiring Diagram
Removing the Motor and Fan Assembly
NOTE: Due to press fit design of composite Rotor on Motor, it is
highly recommended that any time a motor is replaced the fan ro-
tor is replaced as well. The rest of the assembly may be reused.
See Fig. 11.
1.
Unplug motor harness from control box harness and cut
wire tie at the fan deck.
2.
Unplug connectors from stator temperature limit switch.
3.
Remove 2 screws at front of stator on fan deck.
4.
Slide fan assembly forward a couple of inches to clear rear
brackets and lift assembly out.
1
2
3
Fig. 11 — Fan Assembly Removal
8