Compressor; Lubrication - Carrier 50FCQ 04-07 Series Service And Maintenance Instructions

Single package rooftop heat pump with puron (r-410a) refrigerant 3 to 6 nominal tons
Table of Contents

Advertisement

Cooling Charging Chart Std 4 Ton Heat Pump (Three Phase)
R-410A Refrigerant
(Unit must be operated in cooling mode)
1241
180
1172
170
1103
160
1034
150
965
140
896
130
827
120
758
110
689
100
620
90
551
80
30
35
40
45
50
55
–1.1
1.7
4.5
7.2
10.0
12.8
SUCTION LINE TEMPERATURE [°F/°C]
Fig. 25 — Cooling Charging Chart — 4 Ton,
50FCQA05
Cooling Charging Chart Std 5 Ton Heat Pump
R-410A Refrigerant
(Unit must be operated in cooling mode)
1241
180
1172
170
1103
160
1034
150
965
140
896
130
827
120
758
110
689
100
620
90
551
80
30
35
40
45
50
55
-1.1
1.7
4.5
7.2
10.0
12.8
SUCTION LINE TEMPERATURE [°F/°C]
Fig. 26 — Cooling Charging Chart — 5 Ton,
50FCQA06
OUTDOOR
TEMP
°F / °C
115 / 46
105 / 41
95 / 35
85 / 29
75 / 24
65 / 18
55/ 13
45/ 7
60
65
70
75
80
85
90
15.6
18.3
21.1
23.9
26.7
29.5
32.2
48TC003782
A
OUTDOOR
TEMP
°F / °C
115 / 46
105 / 41
95 / 35
85 / 29
75 / 24
65 / 18
55/ 13
45/ 7
60
65
70
75
80
85
90
15.6
18.3
21.1
23.9
26.7
29.5
32.2
48TC003783
A
Cooling Charging Chart Std 6 Ton Heat Pump
(Unit must run in cooling mode, on high stage
compressors & outdoor fan on high speed)
59.9
140
Add Charge if Above the Curve
48.8
120
37.7
100
80
26.6
15.5
60
4.4
40
-6.7
20
150
200
250
1034
1379
1723
Compressor Discharge Pressure, [psig/Kpa]
Fig. 27 — Cooling Charging Chart — 6 Ton,

COMPRESSOR

Lubrication

The compressor is charged with the correct amount of oil at the
factory.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to
components.
The compressor is in a R-410A refrigerant system and uses a
polyolester (POE) oil. This oil is extremely hygroscopic,
meaning it absorbs water readily. POE oils can absorb
15 times as much water as other oils designed for HCFC and
CFC refrigerants. Avoid exposure of the oil to the atmosphere.
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in death, serious
personal injury and/or property damage.
Never use air or gases containing oxygen for leak testing or for
operating refrigerant compressors. Pressurized mixtures of air
or gases containing oxygen can lead to an explosion.
17
R-410A Refrigerant
Remove Charge if Below the Curve
300
350
400
450
500
550
2068
2413
2758
3102
3447
3792
48TC003784
50FCQM07
CAUTION
WARNING
600
4136
A