Carrier 50FCQ 04-07 Series Service And Maintenance Instructions page 55

Single package rooftop heat pump with puron (r-410a) refrigerant 3 to 6 nominal tons
Table of Contents

Advertisement

Table 24 — Dry Bulb Operation with DCV (CO
DEMAND
OUTSIDE AIR
CONTROLLED
GOOD TO
VENTILATION (DCV)
ECONOMIZE
Below CO
Set
2
Above CO
Set
2
NOTE(S):
a. With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second stage cooling
by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
b. With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been
satisfied.
Table 25 — Enthalpy Operation without DCV (CO
DEMAND
OUTSIDE AIR
CONTROLLED
GOOD TO
VENTILATION (DCV)
ECONOMIZE
NO CO
SENSOR
2
NOTE(S):
a. With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second stage cooling
by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
b. With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been
satisfied.
Y1-I
Y2-I
OFF
OFF
No
ON
OFF
ON
ON
OFF
OFF
ON
OFF
Yes
ON
ON
OFF
OFF
No
ON
OFF
ON
ON
OFF
OFF
Yes
ON
OFF
ON
ON
Y1-I
Y2-I
OFF
OFF
NO
ON
OFF
ON
ON
OFF
OFF
ON
OFF
YES
ON
ON
Sensor) — Two-Speed Fan
2
FAN
Y1-O
Y2-O
SPEED
LOW
0-v/Off
0-v/Off
LOW
24-v/On
0-v/Off
HIGH
24-v/On
24-v/On
LOW
0-v/Off
0-v/Off
LOW
0-v/Off
0-v/Off
HIGH
24-v/On
0-v/Off
LOW
0-v/Off
0-v/Off
LOW
24-v/On
0-v/Off
HIGH
24-v/On
24-v/On
LOW
0-v/Off
0-v/Off
LOW
0-v/Off
0-v/Off
DELAY
a
HIGH
0-v/Off
24-v/On
Sensor) — Two-Speed Fan
2
FAN
Y1-O
Y2-O
SPEED
LOW
0-v/Off
0-v/Off
LOW
24-v/On
0-v/Off
HIGH
24-v/On
24-v/On
LOW
0-v/Off
0-v/Off
LOW
0-v/Off
0-v/Off
DELAY
a
HIGH
0-v/Off
24-v/On
55
OCCUPIED
VENTMIN
VENTMIN
VENTMIN
VENTMIN
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
b
Closed to Full-Open
Full-Open
OCCUPIED
MIN POS
MIN POS
MIN POS
MIN POS
MIN POS to Full Open
Closed to Full-Open
MIN POS to Full Open
Closed to Full-Open
b
UNOCCUPIED
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
UNOCCUPIED
Closed
Closed
Closed
Closed

Advertisement

Table of Contents
loading

Table of Contents