Carrier 50FCQ 04-07 Series Service And Maintenance Instructions page 42

Single package rooftop heat pump with puron (r-410a) refrigerant 3 to 6 nominal tons
Table of Contents

Advertisement

Damper Movement
Damper movement from full open to full closed (or vice versa)
takes 2-1/2 minutes.
Thermostats
The EconoMi$er IV control works with conventional thermostats
that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage 1),
W2 (heat stage 2), and G (fan). The EconoMi$er IV control does
not support space temperature sensors. Connections are made at
the thermostat terminal connection board located in the main con-
trol box.
Occupancy Control
The factory default configuration for the EconoMi$er IV control
is occupied mode. Occupied status is provided by the black jump-
er from terminal TR to terminal N. When unoccupied mode is de-
sired, install a field-supplied timeclock function in place of the
jumper between TR and N. When the timeclock contacts are
closed, the EconoMi$er IV control will be in occupied mode.
When the timeclock contacts are open (removing the 24-v signal
from terminal N), the EconoMi$er IV will be in unoccupied
mode.
Demand Controlled Ventilation (DCV)
When using the EconoMi$er IV for demand controlled ventila-
tion, there are some equipment selection criteria which should be
considered. When selecting the heat capacity and cool capacity of
the equipment, the maximum ventilation rate must be evaluated
for design conditions. The maximum damper position must be cal-
culated to provide the desired fresh air.
Typically the maximum ventilation rate will be about 5 to 10%
more than the typical cfm required per person, using normal out-
side air design criteria.
A proportional anticipatory strategy should be taken with the fol-
lowing conditions: a zone with a large area, varied occupancy, and
equipment that cannot exceed the required ventilation rate at de-
sign conditions. Exceeding the required ventilation rate means the
equipment can condition air at a maximum ventilation rate that is
greater than the required ventilation rate for maximum occupancy.
A proportional-anticipatory strategy will cause the fresh air sup-
plied to increase as the room CO
CO
set point has not been reached. By the time the CO
2
reaches the set point, the damper will be at maximum ventilation
and should maintain the set point.
In order to have the CO
sensor control the economizer damper in
2
this manner, first determine the damper voltage output for mini-
mum or base ventilation. Base ventilation is the ventilation re-
quired to remove contaminants during unoccupied periods. The
following equation may be used to determine the percent of out-
side air entering the building for a given damper position. For best
results, there should be at least a 10 degree difference in outside
and return-air temperatures.
OA
(T
) + (T
x
O
100
T
= Outdoor-Air Temperature
O
OA = Percent of Outdoor Air
T
= Return-Air Temperature
R
RA = Percent of Return Air
T
= Mixed-Air Temperature
M
Once base ventilation has been determined, set the minimum
damper position potentiometer to the correct position.
The same equation can be used to determine the occupied or max-
imum ventilation rate to the building. For example, an output of
3.6 volts to the actuator provides a base ventilation rate of 5% and
an output of 6.7 volts provides the maximum ventilation rate of
20% (or base plus 15 cfm per person). Use Fig. 68 to determine
the maximum setting of the CO
1100 ppm set point relates to a 15 cfm per person design. Use the
1100 ppm curve on Fig. 68 to find the point when the CO
level increases even though the
2
level
2
RA
) = T
x
M
100
R
sensor. For example, an
2
sensor
2
output will be 6.7 volts. Line up the point on the graph with the
left side of the chart to determine that the range configuration for
the CO
sensor should be 1800 ppm. The EconoMi$er IV control-
2
ler will output the 6.7 volts from the CO
when the CO
concentration in the space is at 1100 ppm. The
2
DCV set point may be left at 2 volts since the CO
will be ignored by the EconoMi$er IV controller until it rises
above the 3.6 volt setting of the minimum position potentiometer.
Once the fully occupied damper position has been determined, set
the maximum damper demand controlled ventilation potentiome-
ter to this position. Do not set to the maximum position as this can
result in over-ventilation to the space and potential high humidity
levels.
CO
Sensor Configuration
2
The CO
sensor has preset standard voltage settings that can be se-
2
lected anytime after the sensor is powered up.
Use setting 1 or 2 for Carrier equipment.
1.
Press Clear and Mode buttons. Hold at least 5 seconds
until the sensor enters the Edit mode.
2.
Press Mode twice. The STDSET Menu will appear.
3.
Use the Up/Down button to select the preset number.
4.
Press Enter to lock in the selection.
5.
Press Mode to exit and resume normal operation.
The custom settings of the CO
ter the sensor is energized. Follow the steps below to change the
non-standard settings:
1.
Press Clear and Mode buttons. Hold at least 5 seconds
until the sensor enters the Edit mode.
2.
Press Mode twice. The STDSET Menu will appear.
3.
Use the Up/Down button to toggle to the NONSTD menu
and press Enter.
4.
Use the Up/Down button to toggle through each of the
9 variables, starting with Altitude, until the desired setting
is reached.
5.
Press Mode to move through the variables.
6.
Press Enter to lock in the selection, then press Mode to
continue to the next variable.
Dehumidification of Fresh Air with DCV (Demand Con-
trolled Ventilation) Control
If normal rooftop heating and cooling operation is not adequate for
the outdoor humidity level, an energy recovery unit and/or a dehu-
midification option should be considered.
ECONOMI$ER IV PREPARATION
This procedure is used to prepare the EconoMi$er
shooting. No troubleshooting or testing is done by performing the
following procedure.
NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm resis-
tor, and a 5.6 kilo-ohm resistor which are not supplied with the
EconoMi$er IV.
IMPORTANT: Be sure to record the positions of all poten-
tiometers before starting troubleshooting.
1.
Disconnect power at TR and TR1. All LEDs should be off.
Exhaust fan contacts should be open.
2.
Disconnect device at P and P1.
3.
Jumper P to P1.
4.
Disconnect wires at T and T1. Place 5.6 kilo-ohm resistor
across T and T1.
5.
Jumper TR to 1.
6.
Jumper TR to N.
7.
If connected, remove sensor from terminals SO and +.
Connect 1.2 kilo-ohm 4074EJM checkout resistor across
terminals SO and +.
42
sensor to the actuator
2
sensor voltage
2
sensor can be changed anytime af-
2
®
IV for trouble-

Advertisement

Table of Contents
loading

Table of Contents